Belden 9842 Cable 24 AWG 2 Pairs RS-485 Low Capacitance Computer Cable for EIA Applications Multi Conductor Stranded 7x32 TC PVC Jacket Cable

Belden 9842 Cable 24 AWG 2 Pairs RS-485 Low Capacitance Computer Cable for EIA Applications Multi Conductor Stranded 7x32 TC PVC Jacket Cable

Select gauge from drop-down menu for prices:

Belden 9842 Cable 24 AWG 2 Pairs RS-485 Low Capacitance Computer Cable for EIA Applications Multi Conductor Stranded 7x32 TC PVC Jacket Cable

Regular price $5.18 $3.84 Sale /per Foot

Belden 9842 Cable 24 AWG 2 Pairs RS-485 Low Capacitance Computer Cable for EIA Applications Multi Conductor Stranded 7x32 TC PVC Jacket Cable

Description:
• 24 AWG stranded (7x32) TC conductors, polyethylene insulation, twisted pairs, overall Beldfoil® (100% coverage) + TC braid shield (90% coverage), 24 AWG stranded TC drain wire, PVC jacket.

Insulation:
• Material: PE - Polyethylene
• Wall Thickness (in.): 0.022

Outer Shield Drain Wire AWG:
• AWG: 24
• Stranding: 7x32
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (in.): 0.035

Usage (Overall):
Applications:
• RS-485, DMX-512

Mechanical Characteristics (Overall):
• Operating Temperature Range: -30°C To +80°C
• UL Temperature Rating: 80°C
• Bulk Cable Weight: 49 lbs/1000 ft.
• Max. Recommended Pulling Tension: 87 lbs.
• Min. Bend Radius/Minor Axis: 3.500 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CM
• CEC/C(UL) Specification: CM
• AWM Specification: UL Style 2919 (30 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Characteristic Impedance (Ohm): 120
• Nom. Capacitance Conductor to Conductor (pF/ft): 12.8
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/ft): 23
• Nominal Velocity of Propagation: VP (%): 66
• Nominal Delay (ns/ft): 1.540
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 24
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 2.070
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 2.1 Amps/Conductor @ 25°C

Plenum/Non-Plenum:
• Plenum(Y/N): No
• Non-Plenum Number: 82842

technical specification:
awg 24
# pairs 2
stranding 7x32
no. of conductors 4
conductor material tinned copper
diameter (in.) -
outer shield - type tape
outer shield - material aluminum foil-polyester tape
overall cable - nominal diameter (in.) 0.340
belden cable part number 9842

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question