Belden 3072F Cable 18 AWG 1 Pair Blue Hose Twinax DataTray Stranded 7x26 Sunlight Resistant PVC Jacket 600V Cable
Select gauge from drop-down menu for prices:
- Belden Cable Blue Hose 9463 Cable
- Belden 9463 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Sunlight Resistant PVC Jacket Cable
- Belden 9463F Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 42x36 Sunlight Resistant PVC Jacket Cable
- Belden 9463DB Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Sunlight Resistant LDPE Jacket Cable
- Belden 89463 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 FEP Jacket Cable
- Belden 129463 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Aluminum Interlocked Armor PVC Jacket Cable
- Belden 139463 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Steel Interlocked Armor PVC Jacket Cable
- Belden 189463 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Continuously Corrugated Aluminum Armor PVC Jacket Cable
- Belden YR28761 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Heavy-Duty Sunlight Resistant PVC Jacket Cable
- Belden YR41104 Cable 20 AWG 1 Pair Blue Hose Twinax Stranded 7x28 Low Smoke Zero Halogen Jacket Cable
- Belden YR28826 Cable 20 AWG 2 Pairs Blue Hose Twinax Stranded 7x28 Dual Blue PVC Jacket Cable
- Belden YC39151 Cable 20 AWG 2 Pairs Blue Hose Twinax Stranded 7x28 Dual Armored Sunlight Resistant PVC Jacket Cable
Product Details
Description:
• 18 AWG stranded (7x26) tinned copper conductors, flame-retardant polyolefin insulation, overall Beldfoil® (100% coverage) plus a tinned copper braid shield (55% coverage), sunlight resistant PVC jacket.
Insulation:
• Material: FRPO - Flame Retardant Polyolefin
• Diameter (in.): 0.096
Outer Shield Drain Wire AWG:
• AWG: 20
• Stranding: 7x28
• Drain Wire Conductor Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
Mechanical Characteristics (Overall):
• Operating Temperature Range: -40°C To +75°C
• UL Temperature Rating: 75°C Dry
• Bulk Cable Weight: 48 lbs/1000 ft.
• Max. Recommended Pulling Tension: 85 lbs.
• Min. Bend Radius/Minor Axis: 3.250 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC,PLTC, TC
• CEC/C(UL) Specification: CMG
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/13/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
• PMSHA Specification: P-MSHA SC-182/7
Electrical Characteristics (Overall):
• Nom. Charactertistic Impedance: (ohm): 78.000
• Nom. Inductance (μH/ft): 0.12
• Nom. Mutual Capacitance (pF/ft): 19.5
• Nominal Velocity of Propagation: VP (%): 64.5
• Nominal Delay (ns/ft): 1.58
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 6.9
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 3.2
• Max. Operating Voltage - UL: 600 V RMS (NEC Type TC)
• Max. Operating Voltage - UL: 300 V RMS (NEC Type PLTC)
• Max. Operating Voltage - UL: 300 V RMS (NEC Type CMG)
Flame Test:
• UL Flame Test: UL1685 UL Loading
• C(UL) Flame Test: FT4
• IEEE Flame Test: 1202
Suitability:
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 18 |
# pairs | 1 |
stranding | 7x26 |
no. of conductors | 2 |
conductor material | tinned copper |
diameter (in.) | 0.046 |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable - nominal diameter (in.) | 0.324 |
belden cable part number | 3072F |