Belden 1031A 16 AWG 1 Triad 300V PLTC Cable
Select gauge from drop-down menu for prices:
- Belden 16 AWG Triads 300V PLTC Overall Beldfoil Shielding Orange Communication Cable
- Belden 3044A 16 AWG 2 Triads 300V PLTC Cable
- Belden 3046A 16 AWG 4 Triads 300V PLTC Cable
- Belden 3048A 16 AWG 8 Triads 300V PLTC Cable
- Belden 3052A 16 AWG 16 Triads 300V PLTC Cable
- Belden 3054A 16 AWG 24 Triads 300V PLTC Cable
Product Details
Description:
• 16 AWG triads stranded (7x24) bare copper conductors, twisted triads, overall Beldfoil shield (100% coverage), PVC insulation, PVC jacket.
Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.406
Outer Shield Drian Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.940
• Outer Jacket Ripcord: Yes
Pair Lay Length and Direction:
• Twists (twist/m): 6
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• Bulk Cable Weight: 86.762 Kg/Km
• Max. Recommended Pulling Tension: 271.340 N
• Min. Bend Radius/Minor Axis: 28.956 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC-ER, PLTC-ER
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Inductance (?H/m): 0.511836
• Nom. Capacitance Conductor to Conductor (pF/m): 177.502
• Nom. Capacitance Cond. to Other Conductor and Shield (pF/m): 319.241
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 12.1397
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 16.0769
• Max. Operating Voltage - UL: 300 V RMS
Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• CSA Flame Test: FT4
• IEEE Flame Test: 1202
Suitability:
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 16 |
# triads | 1 |
stranding | 7x24 |
no. of conductors | 3 |
conductor material | bare copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 7.239 |
belden cable part number | 1031A |