Belden 1036A 18 AWG 1 Triad 300V PLTC Cable
Select gauge from drop-down menu for prices:
- Belden 18 AWG Triads 300V PLTC Overall Beldfoil Shielding Orange Communication Cable
- Belden 3027A 18 AWG 2 Triads 300V PLTC Cable
- Belden 3030A 18 AWG 4 Triads 300V PLTC Cable
- Belden 3032A 18 AWG 8 Triads 300V PLTC Cable
- Belden 3036A 18 AWG 16 Triads 300V PLTC Cable
- Belden 3038A 18 AWG 24 Triads 300V PLTC Cable
Description:
• 18 AWG triads stranded (7x26) bare copper conductors, twisted triads, PVC insulation, overall Beldfoil shield (100% coverage), PVC jacket.
Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.406
Outer Shield Drian Wire AWG:
• AWG: 20
• Stranding: 7x28
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.9398
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• Bulk Cable Weight: 61.909 Kg/Km
• Max. Recommended Pulling Tension: 361.194 N
• Min. Bend Radius/Minor Axis: 25.400 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC-ER, PLTC-ER
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Inductance (?H/m): 0.55777
• Nom. Capacitance Conductor to Conductor (pF/m): 164.05
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 19.227
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 16.6347
• Max. Operating Voltage - UL: 300 V RMS (PLTC, CMG)
• Max. Operating Voltage - UL: 150 V RMS (ITC)
Flame Test:
• UL Flame Test: UL1685 UL Loading
• CSA Flame Test: FT4
• IEEE Flame Test: 1202
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 18 |
# triads | 1 |
stranding | 7x26 |
no. of conductors | 2 |
conductor material | bare copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 6.375 |
belden cable part number | 1036A |