Belden 26502 16 AWG 1 Triad 300V ACIC Armored Steel Cable
Select gauge from drop-down menu for prices:
- Belden 16 AWG CSA Instrumentation 300V ACIC Armored Individually and Overall Beldfoil Shielded Triads 7x24 Cable
- Belden 23507 16 AWG 1 Triad 300V ACIC Armored Aluminum Cable
- Belden 23522 16 AWG 2 Triads 300V ACIC Armored Aluminum Cable
- Belden 23520 16 AWG 4 Triads 300V ACIC Armored Aluminum Cable
- Belden 23529 16 AWG 6 Triads 300V ACIC Armored Aluminum Cable
- Belden 23526 16 AWG 8 Triads 300V ACIC Armored Aluminum Cable
- Belden 23541 16 AWG 12 Triads 300V ACIC Armored Aluminum Cable
- Belden 23567 16 AWG 16 Triads 300V ACIC Armored Aluminum Cable
- Belden 23578 16 AWG 24 Triads 300V ACIC Armored Aluminum Cable
- Belden 26509 16 AWG 2 Triads 300V ACIC Armored Steel Cable
- Belden 26510 16 AWG 4 Triads 300V ACIC Armored Steel Cable
- Belden 26511 16 AWG 6 Triads 300V ACIC Armored Steel Cable
- Belden 26512 16 AWG 8 Triads 300V ACIC Armored Steel Cable
- Belden 26513 16 AWG 12 Triads 300V ACIC Armored Steel Cable
- Belden 26545 16 AWG 16 Triads 300V ACIC Armored Steel Cable
- Belden 26547 16 AWG 24 Triads 300V ACIC Armored Steel Cable
Product Details
Description:
• 16 AWG triads stranded (7x24) tinned copper conductors, individual Beldfoil plus a polyester isolation tape, PVC insulation, PVC inner jacket, overall Beldfoil shield (100% coverage), drain wires, interlocked armor, PVC outer jacket.
Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.635
Inner Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 8.890
Outer Shield Drain Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Outer Jacket Ripcord: Yes
• Outer Jacket over Armor (y/n): Y
Armor:
• Armor Type: Interlocked
• Armor Material: Steel
Mechanical Charactertistics (Overall):
• Installation Temperature Range: -25°C To +105°C
• Operating Temperature Range: -40°C To +105°C
• Non-UL Temperature Range: 105°C
• Bulk Cable Weight: 295 lbs/1000 ft.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CSA Specification: C22.2#239, Type ACIC, C22.2#174, HLBCD, C22.2#0.3, Clause 4.31, Low Acid Test
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 6.8
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 10
• Max. Operating Voltage - Non-UL: 300 (CSA ACIC)
Flame Test:
• C(UL) Flame Test: FT4
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 16 |
# triads | 1 |
stranding | 7x24 |
no. of conductors | 3 |
conductor material | tinned copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 15.570 |
belden cable part number - steel | 26502 |