Belden 3090AE 16 AWG 1 Pair 600V Multi Conductor PVC/Nylon Insulation Tray Cable

Belden 3090AE 16 AWG 1 Pair 600V Multi Conductor PVC/Nylon Insulation Tray Cable

Regular price $1.80 $1.60 Sale /per Foot

Product Details

Description:
• 16 AWG pairs stranded (7x24) bare copper conductors, twisted pairs, PVC/Nylon insulation, overall Beldfoil shield (100% coverage), drain wire, insulated green ground wire, ripcord, PVC jacket.

Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 16
• Ground Wire Stranding: 7x24
• Ground Wire Conductor Material: BC - Bare Copper
• Ground Wire Insulation Material: PVC/Nylon - Polyvinyl Chloride/Nylon

Insulation:
• Material: PVC/Nylon - Polyvinyl Chloride/Nylon

Outer Shield Drain Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.2192
• Outer Jacket Ripcord: Yes

Mechanical Charactertistics (Overall):
• Wet Temperature Range: -30°C To +75°C
• Dry Temperature Range: -30°C To +90°C
• Bulk Cable Weight: 113.103 Kg/Km
• Max. Recommended Pulling Tension: 578.266 N
• Min. Bend Radius/Minor Axis: 99.060 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: NPLF, TC-ER, UL 1277
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 09/23/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
• Other Specification: ICEA S-73-532, S-61-402

Electrical Characteristics (Overall):
• Nom. Inductance (?H/m): 0.577456
• Nom. Capacitance Conductor to Shield (pF/m): 285.447
• Nom. Mutual Capacitance (pF/m): 164.05
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 12.0413
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 16.3722
• Max. Operating Voltage - UL: 600 V RMS (NEC Type TC)
• Max. Operating Voltage - UL: 150 V RMS (NPLF)

Flame Test:
• UL Flame Test: UL1685 UL Loading
• C(UL) Flame Test: FT4
• IEEE Flame Test: 1202
• ICEA Flame Test: T-29-520

Suitability:
• Suitability - Burial: Yes
• Sunlight Resistance: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No

technical specification:
awg 16
# paris 1
stranding 7x24
no. of conductors 3
conductor material bare copper
outer shield - type tape
outer shield - material aluminum foil-polyester tape
overall cable- nominal dia. (mm) 9.906