Belden 6054 14 and 12 AWG 600V TECK 90 Composite Armored Cable
Select gauge from drop-down menu for prices:
Description:
• Composite 14 AWG stranded (7x22) and 12 AWG stranded (7x20) bare copper conductors, 14 AWG bare copper ground wire, .031x1A;(.79mm) XLPE insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.
Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 14
• Ground Wire Stranding: 7x22
• Conductor Material: BC - Bare Copper
Insulation:
• Material: XLPE - Cross Linked Polyethylene
• Nom. Wall Thickness (mm): 0.787
Inner Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 14.224
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 22.606
Armor:
• Armor Type: Interlocked
• Armor Material: Aluminum
• Diameter over Armor: 0.750
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -40°C To +90°C
• Wet Temperature Range: -40°C To +90°C
• Dry Temperature Range: -40°C To +90°C
• Bulk Cable Weight: 369 lbs/1000 ft.
• Max. Recommended Pulling Tension: 424 lbs.
• Min. Bend Radius/Minor Axis: 8.400 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CSA Specification: CSA C22.2#131; Hazardous Locations CSA C22.2#0.3 Clause 4.31 Low Acid Gas
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 2.5 (14 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 1.65 (12 AWG)
• Max. Recommended Current: 12 Amps/Conductor @ 25°C (14 AWG)
• Max. Recommended Current: 16 Amps/Conductor @ 25°C (12 AWG)
Flame Test:
• CSA Flame Test: FT4
Suitability:
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 14 and 12 |
# conductors | 6 |
stranding | 7x22 and 7x20 |
no. of conductors | 6 |
conductor material | bare copper |
outer shield - material | unshielded |
overall cable- nominal dia. (mm) | 22.606 |
belden cable part number | 6054 |