Description:
• 24 AWG stranded (7x32) TC conductors, conductors cabled, plenum, FEP insulation, overall Beldfoil® (100% coverage), TC braid shield (85% coverage), FEP jacket.
Insulation:
• Material: FEP - Fluorinated Ethylene Propylene
• Wall Thickness (mm): 0.1524
Outer Jacket:
• Material: FEP - Fluorinated Ethylene Propylene
• Nom. Wall Thickness (mm): 0.3556
Overall Cabling Lay Length and Direction:
• Length (mm): 50.8
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -70°C To +200°C
• Bulk Cable Weight: 20 lbs/1000 ft.
• Max. Recommended Pulling Tension: 24 lbs.
• Min. Bend Radius/Minor Axis: 1.500 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMP
• CEC/C(UL) Specification: CMP
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Capacitance Conductor to Conductor (pF/ft): 20
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/ft): 36
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 24.0
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 6.7
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 1.6 Amps/Conductor @ 25°C
Flame Test:
• UL Flame Test: NFPA 262
• CSA Flame Test: FT6
Plenum/Non-Plenum:
• Plenum (Y/N): Yes
technical specification: | |
awg | 24 |
# conductors | 4 |
stranding | 7x32 |
no. of conductors | 4 |
conductor material | tinned copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 3.6576 |
belden cable part number | 83504 |