Technical Data: Special PUR-insulated to UL CSA AWM I/II A/B Style 20939 and CSA
Temperature Range: Flexing -5°C to +80°C fixed installation -40°C to +80°C
Nominal Voltage: UL/CSA 600 V
Test Voltage: 3000 V
Breakdown Voltage: Min. 6000 V
Insulation Resistance: Min. 20 MOhm x km
Minimum Bending Radius: Flexing 10x cable Ø fixed installation 5x cable Ø
Radiation Resistance: Up to 100x106 cJ/kg (up to 100 Mrad) Coupling resistance: max. 250 Ohm/km
Cable Structure:
• Bare copper, fine wire stranded to
DIN VDE 0295 cl.5, BS 6360 cl.5 and IEC 60228 cl.5
• Core insulation of special PVC
compound type TI2 to
DIN VDE 0207-363-3 / DIN EN 50363-3 and UL-Style 10012
• Core identification to DIN VDE 0293
black cores with continuous white
numbering
• GN-YE conductor, 3 cores and above
in the outer layer
• Cores stranded in layers with optimal lay-length
• PVC-insulated inner sheath YM5 to
DIN VDE 0207-363-4-1/ DIN EN 50363-4-1
• Braided screen of tinned Cu wires,
approx. 85% coverage
• Outer sheath of full-polyurethane
• Sheath colour grey (RAL 7001)
• with meter marking
Properties:
• Resistant to mineral oils, synthetic oils and
coolant, UV-radiation, osygene, ozon
and hydrolysis. Conditionally resistant to
microbes.
• The materials used in manufacture are
cadmium-free and contain no silicone
and free from substances harmful to
the wetting properties of lacquers
Note:
• G = with green-yellow conductor
• x = without green-yellow conductor (OZ)
• AWG sizes are approximate equivalent
values. The actual cross-section is in mm².
Unscreened Analogue Type: JZ-602 PUR
Application:
UL and CSA approved flexible control cables up to 600 V, for all machinery in tooling and plant construction, suitable for installation in dry, moist,
wet and outdoor environments for medium mechanical loads. Designed for the export-orientated machinery manufacturer, specifically for USA and
Canada.
EMC = Electromagnetic compatibillity
To optimize the EMC features we recommend a large round contact of the copper braiding on both ends.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.
technical specification: | |
awg-no. | 3/0 |
no.cores x cross-sec.mm² | 4 G 95 |
outer ø app. mm | 50,7 |
cop. weight kg/km | 4060,0 |
weight app. kg/km | 6114,0 |
helukabel part number | 12619 |