General Cable CVTC® XLPE PVC Type PLTC 16/1 Gauge Overall Shielded Pairs Triads Instrumentation Shielded 300V UL

General Cable CVTC® XLPE PVC Type PLTC 16/1 Gauge Overall Shielded Pairs Triads Instrumentation Shielded 300V UL

Select gauge from drop-down menu for prices:

General Cable CVTC® XLPE PVC Type PLTC 16/1 Gauge Overall Shielded Pairs Triads Instrumentation Shielded 300V UL

Product Details

CVTC XLPE PVC Type PLTC 16/1 Gauge Overall Shielded Pairs Triads Instrumentation Shielded 300V UL

Conductor:
• 18 AWG and 16 AWG bare, annealed copper per ASTM B3
• Class B stranding per ASTM B8

Insulation:
• Flame-retardant Cross-linked Polyethylene (XLPE)
• Color-coded per ICEA Method 1: Pairs - black and white; Triads - black, white and red. One conductor in each pair or triad is printed alphanumerically for easy identification

Shield:
Overall shielded pairs/triads: Overall shield is Flexfoil® aluminum/polymer in contact with stranded tinned copper drain wire

Jacket: Lead-free, flame-retardant, sunlight-resistant Polyvinyl Chloride (PVC)

Applications:
• In free air and raceways in accordance with NEC
• Typical applications include audio, intercom, control, energy management and alarm circuits
• In ducts, cable trays or conduit
• In accordance with UL Subject 13 as Power- Limited Circuit Cable
• In Class 3 circuits in accordance with NEC
• Permitted for use in Class I, Division 2 industrial hazardous locations per NEC

Features:
• Rated at 90?C
• Ripcord applied to all cables with jacket thickness of 60 mils or less
• Abrasion- and chemical-resistant
• Excellent electrical properties
• Sunlight- and weather-resistant
• Meets cold bend test at -25?C

Compliances:
Industry Compliances:
• UL 13 Type PLTC, UL File # E36118
• UL 1581
• RoHS Compliant

Flame Test Compliances
• UL 1581/UL 2556 VW-1
• IEEE 383

Other Compliances:
• EPA 40 CFR, Part 261 for leachable lead content per TCLP
• OSHA Acceptable

Packaging: Material cut to length and shipped on non-returnable wood reels

technical specification:
cond. size (awg) 16
no. of pairs/ triads 1
cond.strand 7W
minimum avg. insulation thickness(inches) 0.015
minimum avg. insulation thickness(mm) 0.38
minimum avg. jacket thickness(inches) 0.035
minimum avg. jacket thickness(mm) 0.89
nominal cable o.d.(inches) 0.262
nominal cable o.d.(mm) 6.65
copper weight(lbs/ 1000 ft) 19
copper weight(kg/km) 28
net weight(lbs/ 1000 ft) 42
net weight(kg/km) 63
catalog number 366150*