Conductors:
• 18 AWG - 8 AWG Solid or stranded A nickel
• Class K (18 AWG - 10 AWG) per ASTM B-174
• Class H (8 AWG - 4 AWG) per ASTM B-173
Insulating Construction: High quality reinforced mica tape
Conductor Covering: Ceramic fiber braid coated with a high temperature finish
Outer Braid(Optional): Stainless steel (Not recommended for applications exceeding 700?C)
Characteristics:
• Superior high temperature and oxidation resistance in normal temperatures to 1000?C
• Fire resistant
• Very low smoke emission when burned at rated temperature
• Resistant to many chemicals
• Maintains circuit integrity even when exposed to conditions of high high ambient temperature and flame
• Optional stainless steel braid provides mechanical protection
• If wire is subjected to very rapid rise in temperature, the binder in the construction can ignite but will quickly extinguish. The resulting white ash is non-conductive.
Application:
• For use in non-flexing applications
• Wiring for ovens, kilns, and furnaces
• Where the normal installation environment includes continuous operating temperatures up to 1000?C and intermittent temperatures approaching 1200?C
• Not recommended for outdoor use
Ratings / Approvals:
• 700°C - 600 Volt (Optional SS Braid)
• 1000°C - 300 Volt
• Passes the IEEE-383 (modified) 210,000 BTU/hr Vertical Cable Tray Flame Test
• Passes UL VW-1 Vertical Flame Test
• Passes CSA FT1 Vertical Flame Test
• RoHS Compliant
technical specification: | |
awg. size | 10 |
# strands | 105 |
outer dia. inches | 0.255 |
outer dia. mm | 6.48 |
wgt - lbs per 1000 ft | 68.03 |
wgt - kg per km | 101.23 |
radix wire part number | BTC10N105-AR00-Z3000 |