Description:
3 conductors, stranded, insulated with heat and moisture resistant
crosslinked polyethylene (type XHHW-2), phase identified and cabled
with suitable fillers and 3 symmetrical bare copper ground conductors.
Cable core covered with 5-mil helical copper tape shield and overall
black zero halogen, limited smoke, zero lead jacket.
Application:
For use in ASD/VFD applications.
Suitable for use in hazardous locations:
• Class I - Div 2
• Class II - Div 2
• Class III - Div 1 and 2
Standards:
• UL 1277
• CSA C22.2 #230 TC
• ICEA S-95-658/NEMA WC-70
• Exposed Runs Rated (TC-ER)
Flame Rated:
• IEEE 383 (70,000 BTU)
• IEEE 1202/CSA FT-4
• UL 1685
• Two-hour Firewall
• Temperature Rated at 90°C Wet/Dry Cold Temperature Rated at -40ºC Sunlight Resistant Direct Burial
• Color Code: Method 4
• Zero Halogen, Limited Smoke Jacket
• RoHS Compliant
technical specification: | |
size awg or kcmil | 500 |
strand(no.) | 37 |
insulation thickness(mils) | 65 |
grounding conductors(awg) | 3-#1 |
Jacket Thickness(mils) | 110 |
approx. diameter overall(inch) | 2.23 |
approx. net weight(lb/1000') | 6,677 |
ampacity*(30°c ambient) 90°c wet/dry | 430 |
service wire part number | ASDTCE500/3 |