Prysmian and Draka Cable Power Duct LSZH Duct Flame-retardant Cable
Select gauge from drop-down menu for prices:
Product Details
Design Parameters:
Duct: Modified PE with low smoke and flame-retardant additives. Schedule 40 or Schedule 80 duct is available in sizes from 1 to 3 inches in diameter. Different colors and duct with a molded-in longitudinal stripe for identification are available.
Applications:
• LSZH duct is for use in facilities where flammability and smoke generation are a concern. It is a non-metallic duct made of modified polyethylene (PE) with low-smoke and flame-retardant additives.
• LSZH duct can be supplied as an empty tube, with a pull line or with Draka cables pre-installed. It is shipped with sealed ends to prevent entry of moisture and other contaminants.
Specifications and Ratings:
• GR-356-CORE for Fiber Optic Duct
• ASTM D-2447 Standard Specification for Polyethylene (PE) Plastic Pipe, Schedule 40 and 80, Based on Outside Diameter.
• ASTM D-6070 for physical properties
• NEMA TC-7 Compression & Recovery, 85% minimum
• NEMA TC-7 Crush Resistance, NEMA TC-7 Table 4-1
• NEMA TC-7 Impact Test (room temp), NEMA TC-7: No cracks > 30% max
• NEMA TC-7 Limiting Oxygen Index, ASTM D-2863: 28 minimum
• NEMA TC-7 Environmental Stress Cracking, ASTM D-1693, Test Condition C: No cracks > 20% max, 192 hr. exposure, 100% Igepal CO-630
• NEMA TC-7 Vertical Tray Flame Test UL-1581: No propagation
nominal duct trade size in (mm) |
outer diameter in (mm) |
pipe weight lbs/mft |
minimum bend radius in (mm) |
Action |
1.00 (25.4) | 1.315 (33.4) | 309 | 14 (355) | Request A Quote |
1.25 (31.8) | 1.660 (42.1) | 418 | 17 (432) | Request A Quote |
1.50 (38.1) | 1.900 (48.3) | 500 | 19 (483) | Request A Quote |
2.00 (50.8) | 2.375 (60.3) | 670 | 24 (610) | Request A Quote |
2.50 (63.5) | 2.875 (73.0) | 1047 | 28 (711) | Request A Quote |
3.00 (76.2) | 3.500 (88.9) | 1366 | 42 (1067) | Request A Quote |
3.00 (76.2) | 3.04 (77.3) | 1015 | 1495 | Request A Quote |
Schedule 80 LSZH duct
duct size in (mm) |
outer diameter in (mm) |
wall thickness in (mm) |
minimum physical properties for all duct sizes |
test method | test requirement |
1.00 (25.4) | 1.315 (33.4) | 0.133 (3.4) | compression & recovery | nema tc-7 | 85% minimum |
1.25 (31.8) | 1.660 (42.1) | 0.140 (3.6) | crush resistance | nema tc-7 | nema tc-7 table 4-1 |
1.50 (38.1) | 1.900 (48.3) | 0.145 (3.7) | impact test (room temp) | nema tc-7 | no cracks > 30% max |
2.00 (50.8) | 2.375 (60.3) | 0.154 (3.9) | impact test (-20° c) | nema tc-7 | no cracks > 30% max |
2.50 (63.5) | 2.875 (73.0) | 0.203 (5.2) | limiting oxygen index | astm d-2863 | 28 minimum |
3.00 (76.2) | 3.500 (88.9) | 0.216 (5.5) | environmental stress cracking |
astm d-1693, test condition c 192 hr. exposure, 100% igepal co-630 |
no cracks > 20% max |
vertical tray
flame test
|
ul-1581 | no propagation |