Belden 2/0 AWG CSA Control 1000V TECK 90 Armored Unshielded 19x11 Cable
Select gauge from drop-down menu for prices:
Product Details
Suitable for use in 300V, 600V or some 1000V environments, Belden offers a complete line of unarmored CSA-rated control, instrumentation and power cables.
Combined with a wide range of conductor, insulation and jacket options, Belden has the right cable solution to fit your needs.
Benefits:
• Eliminates the need for costly conduit or burial piping
• Provides superior mechanical protection for use in underground or hazardous environments
• Resists sunlight, chemicals and oil for long-life performance
Features:
• Designed specifically to meet CSA22.2 Type CIC standard
• Wide range of conductor and pair counts
• Armored options available
Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 6
• Conductor Material: BC - Bare Copper
• Ground Wire Insulation Material: Uninsulated
Insulation:
• Material: XLP - Cross Linked Polyolefin
• Wall Thickness (mm): 2.032
Inner Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 2.108
• Nom. Dia. (mm): 35.408
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
Armor:
• Armor Type: Interlocked
• Armor Material: Aluminum
• Diameter over Armor: 1.654
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -40°C To +90°C
• Wet Temperature Range: -40°C To +90°C
• Dry Temperature Range: -40°C To +90°C
• Bulk Cable Weight: 2300 lbs/1000 ft.
• Max. Recommended Pulling Tension: 200 lbs.
• Min. Bend Radius/Minor Axis: 21.100 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 0.085
• Max. Operating Voltage - Other: 1000V (CSA)
• Max. Recommended Current: 195 Amps/Conductor @ 25°C
Flame Test:
• CSA Flame Test: FT4
Suitability:
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
awg | # conductors | overall cable - nominal dia. (mm) |
belden cable part number |
Action |
2/0 | 3 | 44.704 | C5635 | Request A Quote |
2/0 | 4 | 48.971 | 6157 | Request A Quote |