Belden 18 AWG 300V PLTC Individually and Overall Beldfoil Shield Pairs Orange Communication Cable
Select gauge from drop-down menu for prices:
- Belden 1474A 18 AWG 2 Pairs 300V PLTC Multi Conductor Cable
- Belden 1475A 18 AWG 4 Pairs 300V PLTC Multi Conductor Cable
- Belden 1476A 18 AWG 8 Pairs 300V PLTC Multi Conductor Cable
- Belden 1477A 18 AWG 12 Pairs 300V PLTC Multi Conductor Cable
- Belden 3035A 18 AWG 16 Pairs 300V PLTC Multi Conductor Cable
- Belden 1480A 18 AWG 24 Pairs 300V PLTC Multi Conductor Cable
- Belden 1481A 18 AWG 36 Pairs 300V PLTC Multi Conductor Cable
- Belden 3042A 18 AWG 50 Pairs 300V PLTC Multi Conductor Cable
Combine noise protection with flexibility by choosing Type PLTC/ITC cables. Ideally, these cables are used in power-limited circuits for industrial control and energy management systems as well as intercom, audio and alarm applications.
No matter what gauge size, conductor count, insulation, jacket, armor or rating, Belden can meet your needs.
Benefits:
• Savings on material, labor and maintenance with cables rated for exposed runs — no need for conduit
• Superior electrical performance and longer runs in dozens of different environments
• Assured, flexible installation connections with all the necessary ratings
Features:
• Jacket options for excellent resistance to oil, outdoor sunlight/UV, flame and extreme temperatures
• Insulation options for excellent wet electrical performance, oil and chemical resistance and extreme temperature flexiblity
• Conductor options to provide increased flexibilty, greater flex life and corrosion resistance
Insulation:
• Material: PVC - Polyvinyl Chloride
Inner Shield:
• Trade Name: Beldfoil®
• Type: Tape
• Material: Aluminum Foil-Polyester Tape
Inner Shield Drian Wire AWG:
• AWG: 20
• Stranding: 7x28
• Material: TC - Tinned Copper
Outer Shield Drian Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.3462
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• Bulk Cable Weight: 94 lbs/1000 ft.
• Max. Recommended Pulling Tension: 149 lbs.
• Min. Bend Radius/Minor Axis: 4 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC-ER, PLTC-ER
• CEC/C(UL) Specification: CMG
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Capacitance Conductor to Conductor (pF/ft): 51
• Nom. Capacitance Cond. to Other Conductor and Shield (pF/ft): 92
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 6.7 (18 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 16.5 (22 AWG)
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 6
• Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: 10.300 Ohm/1000 ft
• Max. Operating Voltage - UL: 300 V RMs
• Max. Recommended Current: 4 Amps/Conductor @ 25°C
Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• CSA Flame Test: FT4
• IEEE Flame Test: 1202
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
awg | # pairs | overall cable- nominal dia. (mm) |
belden cable part number |
Action |
18 | 2 | 10.414 | 1474A | Request A Quote |
18 | 4 | 12.014 | 1475A | Request A Quote |
18 | 8 | 15.240 | 1476A | Request A Quote |
18 | 12 | 18.771 | 1477A | Request A Quote |
18 | 16 | 21.234 | 3035A | Request A Quote |
18 | 24 | 25.832 | 1480A | Request A Quote |
18 | 36 | 28.677 | 1481A | Request A Quote |
18 | 50 | 35.154 | 3042A | Request A Quote |