Specifications:

  • Plenum: Multi-Pair (UL)
  • CL2P / CMP Unshielded
  • Plenum: [Multi-Pairs (UL) CL2P/CMP Foil Shield: 22 AWG (200°C or 150°C) ] (Color Code Chart)
  • Stranded. (UL) CL2P or CMP. 200°C or 150°C.

Conductor:
Stranded T.C.

Insulation:
FEP or Halar (ECTFE) Add "HL" to P/N

Color Code:
Chart 3

Shield:
Aluminum/Mylar

Jackets Available:

  • FEP (200°C) or
  • PVDF (150°C) Add "K" to P/N or
  • Plenum PVC Jacket available

Industry Approvals:

  • NEC Article 725-CL2P or
  • NEC Article 800-CMP
  • PCC FT6-C(UL) (CMP only)

Impedance: (FEP only)

  • (AWG 22) 85 Ohms Nom.

Vel. of Propagation: (FEP only)
69% Nom.

Capacitance: (FEP only)

  • (AWG 22) 17.6 pF/ft Nom.

Temperature Rating:

    • -80°C to +200°C (FEP/FEP)
    • -20°C to +150°C (FEP/PVDF)
    • -20°C to +150°C (Halar/PVDF)

Put Ups:

  • 1000 Feet (+/- 10%)
  • (Available in Bulk Reels)
Size AWG No. of Pair. Jacket O.D. Inches Aero P/N Action
22 2 .171 2260 Request A Quote
22 3 .182 2360 Request A Quote
22 4 .200 2460 Request A Quote
22 5 .226 2560 Request A Quote
22 6 .234 2660 Request A Quote
22 7 .234 2760 Request A Quote
22 8 .259 2860 Request A Quote
22 9 .280 2960 Request A Quote
22 10 .301 2060 Request A Quote
22 12 .314 2160 Request A Quote
22 13 .322 2160-13 Request A Quote
22 14 .330 2160-14 Request A Quote
22 15 .339 2160-15 Request A Quote
22 16 .356 2160-16 Request A Quote
22 18 .364 2160-18 Request A Quote
22 19 .364 2160-19 Request A Quote
22 20 .372 2160-20 Request A Quote
22 25 .437 2160-25 Request A Quote
22 27 .446 2160-27 Request A Quote
22 37 .496 2160-37 Request A Quote