Lapp OLFLEX® Chain TM Unshielded Flexible Control Cable

Lapp OLFLEX® Chain TM Unshielded Flexible Control Cable

ÖLFLEX® CHAIN TM/TM CY are highly flexible multi conductor tray cables designed for continuous flex applications. ÖLFLEX® CHAIN TM CY has an overall tinned copper braid that provides protection against EMI and RFI. Fine stranding and a specially formulated thermoplastic polymer jacket optimize flex life and provide excellent resistance to mineral oils, synthetic oils, and water-based coolants.

UnShielded Construction
Conductors:
• Finely stranded bare copper
Insulation:
• Specially formulated PVC/nylon; non‑woven wrapping over outer layer
Jacket:
• specially formulated thermoplastic polymer; black
Technical data
Minimum bend radius:
• for continuous flexing: 7.5 x cable diameter:
• - shielded: 10 x cable diameter
Temperature range:
• - UL/CSA TC: -25°C to +90°C
• - for continuous flexing: -25°C to +90°C
• - for stationary use: -40°C to +105°C
Nominal voltage:
• - UL/CSA TC: 600V
• - UL AWM: 1000V
• - IEC U0/U: 300/500V
Test voltage:
• 2000V
Conductor stranding:
• Class 6 super fine wire
Color code:
• black with white numbers,plus green/yellow ground
Approvals:
• UL: TC-ER per UL 1277
MTW per UL 1063
WTTC per UL 2277
submersible pump
PLTC-ER per UL 13
ITC-ER per UL 2250
DP-1 per UL 1690
AWM 20886
• Attributes: UL Oil Res I/II
75°C Wet; 90°C Dry
sunlight resistant
direct burial
NFPA 79
• NEC: Class 1 Division 2 per NEC Article 501
• Canada: c(UL) CIC/TC FT4
CSA AWM I/II A/B FT4
CSA AWM I/II A
• Additional: CE & RoHS
Features
• UL TC-ER reduces material costs, as no conduit is needed
• Multi-standard approval reduces part numbers and cost
• Meets UL Oil Res I/II, resistant to harsh environments for a long service life
• Copper shielding complies with EMC requirements
• Resistant to a wide range of disinfecting solutions used in the food, beverage, chemical and related industries, according to ECOLAB® PM 40-1 test procedure

AWG No. of Conductors
(incl. ground)
Nominal Outer
Diameter
Copper Weight
(lbs/mft)
Approx. Weight
(lbs/mft)
Part Number
inches mm
18 AWG (1 mm²)
18 3 0.308 7.8 20 44 8718030
18 4 0.337 8.6 26 55 8718040
18 5 0.365 9.3 33 64 8718050
18 7 0.423 10.7 46 84 8718070
18 12 0.486 12.3 79 141 8718120
18 18 0.606 15.4 118 207 8718180
18 25 0.699 17.8 164 278 8718250
16 AWG (1.5 mm²)
16 3 0.340 8.6 29 62 8716030
16 4 0.373 9.5 39 75 8716040
16 5 0.405 10.3 49 90 8716050
16 7 0.473 12.0 68 121 8716070
16 12 0.580 14.7 112 209 8716120
16 18 0.679 17.2 175 298 8716180
16 25 0.786 20.0 242 417 8716250
14 AWG (2.5 mm²)
14 4 0.419 10.6 65 121 8714040
14 7 0.570 14.5 113 192 8714070
12 AWG (4 mm²)
12 4 0.487 12.4 104 198 8712040
10 AWG (6 mm²)
10 4 0.600 15.2 155 267 8710040

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question