Prysmian Cable 35kV TRXLPE URD 133% Copper Medium Voltage Utility Cables

Prysmian Cable 35kV TRXLPE URD 133% Copper Medium Voltage Utility Cables

Select gauge from drop-down menu for prices:

Prysmian Cable 35kV TRXLPE URD 133% Copper Medium Voltage Utility Cables

Product Details

Conductors: Solid or Class B Compressed concentric strand Aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.

Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes and NESC lightning bolt symbol.

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.

Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• Multiplex cables
• Tinned round and flat strap neutrals
• Compact stranded conductors
• Strandseal®
• Super smooth conductor shield
• UL MV-90 Rating if required
• 46kV
• RUS Bulletin 1728F-U1 where applicable

Installation:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary

Specifications and ratings:
• AEIC- AEIC CS8
• ICEA- ICEA S-94-649
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.

conductor insulation
thickness
(mils)
concentric
neutral
cond.
dia.(in)
ins.
dia.
(in)
ins.
shield
diameter (in)
jacket
dia.(in)
cable
weight
(lbs/kft)
min.
bending
radius (in)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)
prysmian
cable
part
number
(a) (b) (c) (d) 90°c in duct 90°c direct buried
35kv 133% copper single phase - full neutral
1/0 solid cu 420 16-#12 0.325 1.22 1.31 1.58 1386 13 215 256 36 276 256 36 QC7010A
1/0 awg cu 420 16-#12 0.364 1.26 1.35 1.62 1425 13 217 258 34 278 258 35 QC8010A
2/0 awg cu 420 13-#10 0.408 1.30 1.39 1.76 1742 15 248 203 33 316 203 33 QC9010A
3/0 awg cu 420 16-#10 0.458 1.35 1.44 1.81 1981 15 281 163 31 358 163 31 QCA010A
4/0 awg cu 420 16-#9 0.515 1.41 1.50 1.90 2319 16 319 130 30 402 130 30 QCB010A
35kv 133% copper three phase - one-third neutral
1/0 solid cu 420 9-#14 0.325 1.22 1.31 1.55 1160 13 216 126 54 277 137 97 QC7000A
1/0 awg cu 420 9-#14 0.364 1.26 1.35 1.58 1197 13 216 129 53 278 139 95 QC8000A
2/0 awg cu 420 11-#14 0.408 1.30 1.39 1.63 1340 14 245 103 51 311 115 92 QC9000A
3/0 awg cu 420 14-#14 0.458 1.35 1.44 1.74 1587 14 278 82 49 347 96 87 QCA000A
4/0 awg cu 420 18-#14 0.515 1.41 1.50 1.80 1816 15 314 66 47 383 83 83 QCB000A
250 MCM cu 420 21-#14 0.561 1.46 1.55 1.85 2022 15 344 57 47 409 74 79 QCC000A
350 MCM cu 420 18-#12 0.664 1.57 1.68 2.02 2595 17 408 42 44 461 62 70 QCD000A
500 MCM cu 420 17-#10 0.794 1.70 1.81 2.19 3401 18 480 32 42 510 53 59 QCE000A
750 MCM cu 420 20-#9 0.974 1.88 2.00 2.40 4637 20 561 25 38 573 44 47 QCF000A
1000 MCM cu 420 21-#8 1.124 2.03 2.15 2.58 5846 21 609 22 36 626 38 39 QCG000A