General Cable Type MC-HL CSA Type HL EPR Armored Power 8 kV Shielded 3/C VFD UL Cable Tray Use Sunlight-Resistant Direct Burial ABS CWCMC CCW®

General Cable Type MC-HL CSA Type HL EPR Armored Power 8 kV Shielded 3/C VFD UL Cable Tray Use Sunlight-Resistant Direct Burial ABS CWCMC CCW®

Select gauge from drop-down menu for prices:

General Cable Type MC-HL CSA Type HL EPR Armored Power 8 kV Shielded 3/C VFD UL Cable Tray Use Sunlight-Resistant Direct Burial ABS CWCMC CCW®

Product Details

Conductor: 
• Bare annealed copper per ASTM B3 
• Compact stranding per ASTM B496 

Extruded Strand Shield (ESS): Extruded thermoset semi-conductor stress control layer over the conductor per ICEA S-93-639 and UL 1072 

Insulation: 140 mils Ethylene Propylene Rubber (EPR) insulation per ICEA S-93-639 and UL 1072 

Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer, free stripping from the insulation per ICEA S-93-639 and UL 1072 

Shield: 5 mil annealed bare copper tape with 25% overlap 

Phase Identification: Color-coded polymeric identification tape laid under the shield - black, red and blue 

Grounding Conductors: 
• Three (3) split Class B stranded bare annealed copper grounding conductors 
• Sized in accordance with UL 1072 and NEC Article 250 

Cable Assembly: 
• Insulated and grounding conductors are cabled together with nonhygroscopic fillers when required 
• Binder tape is applied over the cabled core 

CCW Armor: 
• Impervious, continuously welded and corrugated aluminum alloy sheath per UL 1072 and UL 1569 
• CCW armor conductivity meets the grounding requirements of the NEC 

Jacket: 
• Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), yellow 
• Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C 

Applications: 
• Variable Frequency Drives: 3-conductor CCW armored cables with three (3) symmetrical grounding wires are the preferred wiring method for use with AC     motors controlled by pulse-width modulated inverters in VFD applications 
• CCW armored medium-voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods 
• For use on feeders and branch circuits in industrial power distribution systems per NEC Articles 328 and 330 
• For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502, 503 and 505 
• Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart 
• Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete 
• Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute 

Features: 
• CCW armor provides an impervious barrier to moisture, gas and liquids and meets the grounding requirements of UL 1072 and the NEC 
• Triple Extrusion: The strand shield, EPR insulation and insulation shield are all extruded in one operation 
• General Cable’s EPR insulation system has outstanding corona resistance and high dielectric strength, and it provides electrical stability under stress 
• Cable meets cold impact at -40°C 
• 105°C continuous operating temperature, wet or dry 
• 140°C emergency rating 
• 250°C short circuit rating 

Specifications: 
Design Adherence: 
• ICEA S-93-639/WC74, 5-46 kV Shielded Power Cable 
• AEIC CS8 Specification for Shielded Power Cable, 5-46 kV 
• UL 1072 Medium-Voltage Power Cables 
• UL 1569 Metal Clad Cables 
• UL 2225 Cables and Cable Fittings for Use in Hazardous Locations 
• UL 1309 Marine Shipboard Cable 
• CSA 68.10 

Flame Tests: 
• ICEA T-29-520 (210,000 BTU/hr) 
• IEEE 383 (70,000 BTU/hr) 
• CSA FT4 
• IEEE 1202 (70,000 BTU/hr) 
• UL 1072 
• IEC 60332-3 Category A 

Compliances: 
• UL Type MV-105 or MC-HL, SUN RES, CT USE, DIR BUR, -40°C, FT4, UL File # E90501 
• UL Listed Marine Shipboard, UL File # E85994 
• CSA Type HL, SR, FT4, -40°C, CSA File # 27161 
• American Bureau of Shipping (ABS) Listed for CWCMC

cond.
size
no.
of
cond.
insulation
thickness
nominal
o.d.
over
insulation
bare
ground
nominal
core
o.d.
nominal
armor
o.d.
jacket
thickness
nominal
overall
o.d.
approximate
net
weight
ampacity general cable
part number
awg (kcmil) mils mm inches mm awg inches mm inches mm mils mm inches mm lbs/1000
ft
kg/1000m
in air¹ direct
burial²
3/C WITH GROUND MC-HL OR MV-105, 140 MILS EPR, 8 kV 133% INSULATION LEVEL
6 (7/w)
(13.3 mm²)
3 140 3.6 0.48 12.2 3 x #10 1.20 30.5 1.60 40.6 60 1.52 1.73 43.9 1,350 2,009 105 120 9815.00603310
4 (7/w)
(21.2 mm²)
3 140 3.6 0.53 13.5 3 x #10 1.29 32.8 1.70 43.2 60 1.52 1.83 46.5 1,600 2,381 135 155 9815.00403310
2 (7/w)
(33.6 mm²)
3 140 3.6 0.58 14.7 3 x #10 1.42 36.1 1.85 47.0 60 1.52 1.98 50.3 2,000 2,976 185 200 9815.00203310
1 (19/w) 3 140 3.6 0.62 15.7 3 x #8 1.52 38.6 1.93 49.0 60 1.52 2.06 52.3 2,275 3,386 210 225 9815.00103308
1/0 (19/w)
(53.5 mm²)
3 140 3.6 0.65 16.5 3 x #8 1.61 40.9 2.03 51.6 60 1.52 2.16 54.9 2,600 3,869 240 255 9815.11003308
2/0 (19/w)
(67.4 mm²)
3 140 3.6 0.69 17.5 3 x #8 1.66 42.2 2.14 54.4 60 1.52 2.27 57.7 2,950 4,390 275 290 9815.21003308
4/0 (19/w)
(107 mm²)
3 140 3.6 0.79 20.1 3 x #7 1.87 47.5 2.40 61.0 75 1.91 2.56 65.0 4,025 5,990 360 375 9815.41003307
250 (37/w)
(127 mm²)
3 140 3.6 0.85 21.6 3 x #6 2.06 52.3 2.59 65.8 75 1.91 2.75 69.9 4,600 6,846 400 410 9815.25003306
350 (37/w)
(177 mm²)
3 140 3.6 0.94 23.9 3 x #6 2.15 54.6 2.85 72.4 75 1.91 3.01 76.5 5,800 8,631 490 495 9815.35003306
500 (37/w)
(253 mm²)
3 140 3.6 1.06 26.9 3 x #5 2.44 62.0 3.19 81.0 85 2.16 3.37 85.6 7,800 11,608 600 590 9815.50003305
750 (61/w)
(380 mm²)
3 140 3.6 1.26 32.0 3 x #4 3.19 81.0 3.68 93.5 85 2.16 3.86 98.0 10,750 15,998 745 720 9815.75003304
1000 (61/w)
(507 mm²)
3 140 3.6 1.42 36.1 3 x #4 3.48 88.4 3.98 101.1 85 2.16 4.16 105.7 13,550 20,165 860 810 9815.10003304