General Cable Low-Smoke Zero-Halogen® 120V DeviceNet-Compatible Cable Two Pair Composite Shielded Sheathed ABS Type Approved ETL Confirmed

General Cable Low-Smoke Zero-Halogen® 120V DeviceNet-Compatible Cable Two Pair Composite Shielded Sheathed ABS Type Approved ETL Confirmed

Select gauge from drop-down menu for prices:

General Cable Low-Smoke Zero-Halogen® 120V DeviceNet-Compatible Cable Two Pair Composite Shielded Sheathed ABS Type Approved ETL Confirmed

Product Details

1 Pair 16 AWG Shielded
Conductor: 16 AWG 19/.0117 tinned copper: .056" nom. O.D.

Insulation: Low-Smoke, Zero-Halogen Polyolefin, .022" nom. wall: .100" nom. O.D.

Color Code: C1: Red C2: Black

Shield: Aluminum/Polyester tape 25% overlap 100% coverage (aluminum side out)

1 Pair 18 AWG Shielded
Conductor: 18 AWG 19/30 tinned copper: .049" nom. O.D.

Insulation: Foam Polyolefin, .053" nom. wall: .155" nom. O.D.

Color Code: C1: Blue C2: White

Shield: Aluminum/Polyester tape 25% overlap 100% coverage (aluminum side out)

Final Assembly 2 Pairs Cabled Left-Hand Lay
Drain Wire: 16 AWG 19/29 tinned copper

Overall Shield: 36 AWG tinned copper, 65% min. coverage

Sheath: Low-Smoke, Zero-Halogen, .060" nom. wall, Black: .475" nom. O.D.

Cable Weight: 125 lbs/kft nom.

Features:
• Mechanically enhanced construction renders the cable suitable for installation in cable tray as an interconnect cable
• Suitable for installation in vessels’ quarters area

Compliances:
• Flammability: IEC 60332-3-22 Category A
• Smoke: IEC 61034-1 & -2, MIL-DTL-24643B and NES 711
• Halogen Content: IEC 60754-1 & -2
• Toxicity: MIL-DTL-24643B and NES 713
• Acidity: IEC 60754-1 & -2 and MIL-DTL-24643B

Third-Party Testing:
ETL has tested and confirmed that this product complies with the above specifications
(report number 3316259CRT-004)

Electrical Characteristics
1/Pair 16 AWG Shielded
Conductor DCR: 4.39 V/kft nom.

1/Pair 18 AWG Shielded
Conductor DCR: 6.1 V/kft nom.
Capacitance: 12.0 pF/ft nom.
Impedance: 120 ± 10 V @ 1 MHz
Velocity of Propagation: 76% nom.
Temperature & Voltage Ratings: -30°C to +75°C/300 V Max.

Attenuation (Nom.):

freq.(mhz)
db/100 ft
0.125 0.13
0.50 0.25
1.0 0.40