General Cable EmPowr® 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation
Select gauge from drop-down menu for prices:
- General Cable EmPowr® 2 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 1 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 1/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 2/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 3/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 4/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 250kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 350kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 500kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 1000kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
- General Cable EmPowr® 1 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 2 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 1/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 2/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 3/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 4/0 AWG 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 250kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 350kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 500kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
- General Cable EmPowr® 1000kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 220 mils
Product Details
Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97- 682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable.
Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.
Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer.
Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III.
Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation.
Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator.
Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC).
Features and Benefits:
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Flexibility for easy handling
• Excellent moisture resistance
• Deformation-resistant
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield without the use of a release agent
• Sunlight-resistant
Temperature Rating:
• Normal - 105°C
• Emergency* - 140°C
• Short Circuit - 250°C
Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.
Options:
• Copper conductors
• EmPowr® Fill LF Lead-Free EAM
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• Dry nitrogen cure
• True Triple Extrusion
• 3 X 1/C triplex or parallel
• Type MV-105 UL 1072
• UL Listedb
compressed conductor |
copper
neutral
|
diameter (1)
inches
|
nominal
jacket
thkn.
inches(1)
|
approx. weight (1)
lb/1000 ft
|
ampacity (2) | |||||||
al
awg/
kcmil
|
no.
of
wires
|
no.
of
wires
|
wire
size
awg
|
insulation |
pvc
jacket
|
al
cond.
|
cu
shield /wires |
total |
direct
buried
|
in
duct
|
||
min. | max. | |||||||||||
175 mils nominal epr insulation – 15 kv 100% level | ||||||||||||
2 | 7 | 9 | 24 | 0.635 | 0.720 | 0.937 | 0.080 | 62 | 12 | 388 | 165 | 125 |
1 | 19 | 6 | 22 | 0.675 | 0.760 | 0.987 | 0.080 | 78 | 13 | 424 | 190 | 145 |
1/0 | 19 | 7 | 22 | 0.715 | 0.800 | 1.027 | 0.080 | 99 | 15 | 468 | 215 | 165 |
2/0 | 19 | 7 | 22 | 0.760 | 0.845 | 1.071 | 0.080 | 125 | 15 | 517 | 245 | 185 |
3/0 | 19 | 7 | 22 | 0.810 | 0.895 | 1.121 | 0.080 | 158 | 15 | 576 | 280 | 215 |
4/0 | 19 | 8 | 22 | 0.865 | 0.950 | 1.177 | 0.080 | 199 | 17 | 649 | 320 | 245 |
250 | 37 | 8 | 22 | 0.920 | 1.005 | 1.233 | 0.080 | 234 | 17 | 716 | 355 | 275 |
350 | 37 | 9 | 22 | 1.015 | 1.100 | 1.336 | 0.080 | 329 | 19 | 868 | 430 | 335 |
500 | 37 | 6 | 20 | 1.150 | 1.235 | 1.477 | 0.080 | 468 | 20 | 1080 | 525 | 410 |
750 | 61 | 7 | 20 | 1.340 | 1.425 | 1.664 | 0.080 | 703 | 23 | 1422 | 660 | 510 |
1000 | 61 | 8 | 20 | 1.485 | 1.575 | 1.873 | 0.110 | 937 | 27 | 1840 | 765 | 615 |
220 mils nominal epr insulation – 15 kv 133% level | ||||||||||||
2 | 7 | 9 | 24 | 0.725 | 0.815 | 1.027 | 0.080 | 62 | 12 | 457 | 165 | 125 |
1 | 19 | 7 | 22 | 0.765 | 0.855 | 1.077 | 0.080 | 78 | 15 | 498 | 190 | 145 |
1/0 | 19 | 7 | 22 | 0.805 | 0.895 | 1.117 | 0.080 | 99 | 15 | 543 | 215 | 165 |
2/0 | 19 | 8 | 22 | 0.850 | 0.935 | 1.161 | 0.080 | 125 | 17 | 597 | 245 | 185 |
3/0 | 19 | 8 | 22 | 0.900 | 0.985 | 1.211 | 0.080 | 158 | 17 | 660 | 280 | 215 |
4/0 | 19 | 8 | 22 | 0.955 | 1.045 | 1.267 | 0.080 | 199 | 17 | 735 | 320 | 245 |
250 | 37 | 9 | 22 | 1.010 | 1.100 | 1.323 | 0.080 | 234 | 19 | 808 | 350 | 275 |
350 | 37 | 6 | 20 | 1.105 | 1.190 | 1.439 | 0.080 | 329 | 20 | 968 | 425 | 335 |
500 | 37 | 7 | 20 | 1.240 | 1.330 | 1.567 | 0.080 | 468 | 23 | 1189 | 520 | 410 |
750 | 61 | 8 | 20 | 1.430 | 1.520 | 1.814 | 0.110 | 703 | 27 | 1641 | 655 | 510 |
1000 | 61 | 9 | 20 | 1.575 | 1.670 | 1.963 | 0.110 | 937 | 30 | 1979 | 765 | 615 |