General Cable EmPowr® 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation

General Cable EmPowr® 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation

Select gauge from drop-down menu for prices:

General Cable EmPowr® 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation

Product Details

Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97- 682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable. 

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum. 

Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer. 

Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III. 

Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation. 

Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator. 

Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC). 

Features and Benefits: 
• Triple-extruded for clean interfaces 
• Class 10,000 environment utilized for cable core material handling 
• Flexibility for easy handling 
• Excellent moisture resistance 
• Deformation-resistant 
• High dielectric strength 
• Low dielectric loss 
• Excellent resistance to water treeing 
• Clean-stripping insulation shield without the use of a release agent 
• Sunlight-resistant 

Temperature Rating: 
• Normal - 105°C 
• Emergency* - 140°C 
• Short Circuit - 250°C

Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried. 

Options: 
• Copper conductors 
• EmPowr® Fill LF Lead-Free EAM 
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610 
• Dry nitrogen cure 
• True Triple Extrusion 
• 3 X 1/C triplex or parallel 
• Type MV-105 UL 1072 
• UL Listedb

compressed
conductor
copper
neutral
diameter (1)
inches
nominal
jacket
thkn.
inches(1)
approx. weight (1)
lb/1000 ft
ampacity (2)
al
awg/
kcmil
no.
of
wires
no.
of
wires
wire
size
awg
insulation
pvc
jacket
al
cond.
cu
shield
/wires
total
direct
buried
in
duct
min. max.
175 mils nominal epr insulation – 15 kv 100% level
2 7 9 24 0.635 0.720 0.937 0.080 62 12 388 165 125
1 19 6 22 0.675 0.760 0.987 0.080 78 13 424 190 145
1/0 19 7 22 0.715 0.800 1.027 0.080 99 15 468 215 165
2/0 19 7 22 0.760 0.845 1.071 0.080 125 15 517 245 185
3/0 19 7 22 0.810 0.895 1.121 0.080 158 15 576 280 215
4/0 19 8 22 0.865 0.950 1.177 0.080 199 17 649 320 245
250 37 8 22 0.920 1.005 1.233 0.080 234 17 716 355 275
350 37 9 22 1.015 1.100 1.336 0.080 329 19 868 430 335
500 37 6 20 1.150 1.235 1.477 0.080 468 20 1080 525 410
750 61 7 20 1.340 1.425 1.664 0.080 703 23 1422 660 510
1000 61 8 20 1.485 1.575 1.873 0.110 937 27 1840 765 615
220 mils nominal epr insulation – 15 kv 133% level
2 7 9 24 0.725 0.815 1.027 0.080 62 12 457 165 125
1 19 7 22 0.765 0.855 1.077 0.080 78 15 498 190 145
1/0 19 7 22 0.805 0.895 1.117 0.080 99 15 543 215 165
2/0 19 8 22 0.850 0.935 1.161 0.080 125 17 597 245 185
3/0 19 8 22 0.900 0.985 1.211 0.080 158 17 660 280 215
4/0 19 8 22 0.955 1.045 1.267 0.080 199 17 735 320 245
250 37 9 22 1.010 1.100 1.323 0.080 234 19 808 350 275
350 37 6 20 1.105 1.190 1.439 0.080 329 20 968 425 335
500 37 7 20 1.240 1.330 1.567 0.080 468 23 1189 520 410
750 61 8 20 1.430 1.520 1.814 0.110 703 27 1641 655 510
1000 61 9 20 1.575 1.670 1.963 0.110 937 30 1979 765 615