Product Details
Specifications:
- HW 220 Power Cable
- 5KV/8KV UL Type MV-105-LS, 105°C
- Single Conductor, Shielded
- EPR Insulation
- Low Smoke Zero Halogen Jacket
- 5KV 133%, 8KV 100% Insulation Level
- Copper Conductor
Application:
LifeGuard™ Low Smoke Zero Halogen cable is for use in power circuits in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. It may be installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. It is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard™ cable is ideal for applications where a high degree of safety and equipment protection is required.
It is National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
- Product Features:
- Cable tray rated on sizes 1/0 AWG and larger
- Sunlight-resistant
- Approved for direct burial
- Very low smoke production when burned
- Highly chemical resistant
- Very flame retardant
- Burns to an ash - does not exhibit thermoplastic drip
- Excellent compression and impact resistance
- Superior tensile strength and abrasion resistance
- Flexible jacket with low coefficient of friction
Conductors:
Compressed soft annealed copper per ASTM B-3, Class B stranding per ASTM B-8, with a semi-conducting conductor shield
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682 Type III with a semi-conducting insulation shield
Shield:
Uncoated copper tape with a 25% overlap per ICEA S-97-682
Jacket:
Sunlight-resistant and flame-retardant, Low Smoke Zero Halogen polyolefin per UL Standard 1072 and ICEA T-33-655-1994 Section 5-4
Flame Tests:
- IEEE 383 70,000 BTU/hr flame test
- IEEE 1202 70,000 BTU/hr flame test
- UL Standard 1685 70,000 BTU/hr Flame Propagation and Smoke Release Test
Additional Standards:
AEIC C5-8
Size (AWG or kcmil) |
No. of Strands |
Net Weight | Overall Diameter (Inches) |
Insulation Thickness (Mils) |
Jacket Thickness (Mils) |
Insulation Diameter (Inch) |
Product Code |
6 Gauge | 7 | 286 | 0.63 | 115 | 60 | 0.43 | HW220 00601 / HW22000601 |
4 Gauge | 7 | 350 | 0.71 | 115 | 60 | 0.50 | HW220 00401 / HW22000401 |
2 Gauge | 7 | 460 | 0.77 | 115 | 60 | 0.56 | HW220 00201 / HW22000201 |
1 Gauge | 19 | 565 | 0.81 | 115 | 60 | 0.60 | HW220 00101 / HW22000101 |
1/0 | 19 | 620 | 0.84 | 115 | 60 | 0.64 | HW220 10101 / HW22010101 |
2/0 | 19 | 755 | 0.93 | 115 | 80 | 0.68 | HW220 20101 / HW22020101 |
3/0 | 19 | 890 | 0.99 | 115 | 60 | 0.73 | HW220 30101 / HW22030101 |
4/0 | 19 | 1055 | 1.04 | 115 | 80 | 0.79 | HW220 40101 / HW22040101 |
250 MCM | 37 | 1205 | 1.09 | 115 | 80 | 0.85 | HW220 25001 / HW22025001 |
350 MCM | 37 | 1570 | 1.20 | 115 | 80 | 0.95 | HW220 35001 / HW22035001 |
500 MCM | 37 | 2115 | 1.34 | 115 | 80 | 1.08 | HW220 50001 / HW22050001 |
750 MCM | 61 | 2995 | 1.53 | 115 | 80 | 1.27 | HW220 75001 / HW22075001 |
1000 MCM | 61 | 3870 | 1.68 | 115 | 80 | 1.42 | HW220 10001 / HW22010001 |