Belden 22 AWG 300V PLTC Overall Beldfoil Shielding Orange Communication Cable

Belden 22 AWG 300V PLTC Overall Beldfoil Shielding Orange Communication Cable

Product Details

Combine noise protection with flexibility by choosing Type PLTC/ITC cables. Ideally, these cables are used in power-limited circuits for industrial control and energy management systems as well as intercom, audio and alarm applications.

No matter what gauge size, conductor count, insulation, jacket, armor or rating, Belden can meet your needs.

Benefits:
• Savings on material, labor and maintenance with cables rated for exposed runs — no need for conduit
• Superior electrical performance and longer runs in dozens of different environments
• Assured, flexible installation connections with all the necessary ratings

Features:
• Jacket options for excellent resistance to oil, outdoor sunlight/UV, flame and extreme temperatures
• Insulation options for excellent wet electrical performance, oil and chemical resistance and extreme temperature flexiblity
• Conductor options to provide increased flexibilty, greater flex life and corrosion resistance

Insulation:
• Material: F-R PVC - Flame Retardant Polyvinyl Chloride
• Dia. (mm): 1.5748

Outer Shield Drian Wire AWG:
• AWG: 22
• Stranding: 7x30
• Material: TC - Tinned Copper

Outer Jacket:
• Material: F-R PVC - Flame Retardant Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.0922
• Outer Jacket Ripcord: Yes

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• UL Temperature Rating: 105°C
• Bulk Cable Weight: 55.063 Kg/Km
• Max. Recommended Pulling Tension: 204.617 N
• Min. Bend Radius/Minor Axis: 76.200 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC-ER, PLTC-ER
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Surface Printing (Overall):
Electrical Characteristics (Overall):
• Nom. Inductance (?H/m): 0.6562
• Nom. Capacitance Conductor to Conductor (pF/m): 85.306
• Nom. Capacitance Cond. to Conductor and Shield (pF/m): 157.488
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 49.215
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 49.215
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 2.4 Amps/Conductor @ 25°C

Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• C(UL) Flame Test: FT4
• IEEE Flame Test: 1202

Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Suitability - Burial: Yes
• Sunlight Resistance: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No

awg # pairs overall cable-
nominal dia. (mm)
belden cable
part number
Action
22 2 7.874 3000A Request A Quote
22 4 9.068 3004A Request A Quote
22 8 11.430 3006A Request A Quote
22 12 13.614 3008A Request A Quote
22 16 15.088 3010A Request A Quote
22 24 19.025 3012A Request A Quote
22 50 25.832 3014A Request A Quote

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question