Prysmian Cable 25kV 100% Aluminum TRXLPE URD CSA Medium Voltage Utility Cables

Prysmian Cable 25kV 100% Aluminum TRXLPE URD CSA Medium Voltage Utility Cables

Select gauge from drop-down menu for prices:

Prysmian Cable 25kV 100% Aluminum TRXLPE URD CSA Medium Voltage Utility Cables

Product Details

Conductor: Solid or Class B compact or compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.

Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes.

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.

Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• EPROTENAX™ (EPR) insulation
• Multiplex cables
• Tinned round and flat strap neutrals
• Strandseal®
• Super smooth conductor shield
• Cables made to AEIC CS8 and/or ICEA S-94-649
• 46kV

Installations:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary

Specifications and Ratings:
• CSA - CSA C68.5 -40°C
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.

conductor insulation
thickness
(mils)
concentric
neutral
cond.
dia.(in)
ins.
dia.
(in)
ins.
shield
diameter (in)
jacket
dia.(in)
cable
weight
(lbs/kft)
min.
bending
radius (in)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)
prysmian
cable
part
number
(a) (b) (c) (d) 90°c in duct 90°c direct buried
25kv 100% aluminum single phase - full neutral
1 solid al 260 13-#14 7.34 21.97 23.85 29.95 957 254 145 1.70 0.11 192 1.70 0.11 Q9N01ZC
1 awg al 260 13-#14 7.65 22.17 24.05 30.15 966 254 146 1.72 0.10 194 1.72 0.10 Q9O01ZC
1/0 solid al 260 16-#14 8.26 22.89 24.77 30.87 1070 254 165 1.36 0.10 218 1.36 0.10 Q9P01ZC
1/0 awg al 260 16-#14 8.59 23.11 24.99 31.09 1081 254 166 1.38 0.10 229 1.38 0.10 Q9Q01ZC
2/0 awg al 260 13-#12 9.60 24.13 26.01 32.96 1276 279 190 1.08 0.09 250 1.08 0.09 Q9R01ZC
3/0 awg al 260 16-#12 10.82 25.35 27.23 34.18 1451 279 217 0.86 0.09 283 0.86 0.09 Q9S01ZC
4/0 awg al 260 20-#12 12.14 26.67 29.01 35.96 1652 305 247 0.69 0.09 322 0.69 0.09 Q9T01ZC
250 MCM al 260 23-#12 13.28 28.07 30.35 37.35 1926 305 276 0.56 0.08 356 0.56 0.08 Q9U01ZC
350 MCM al 260 33-#12 15.72 30.51 32.84 39.79 2448 330 326 0.42 0.08 418 0.42 0.08 Q9V01ZC
25kv 100% aluminum three phase - one-third neutral
1 solid al 260 10-#16 7.34 21.97 23.85 29.28 808 254 146 0.86 0.17 196 0.88 0.33 Q9N00ZC
1 awg al 260 10-#16 7.65 17.75 19.63 25.06 818 254 146 0.87 0.17 197 0.90 0.32 Q9O00ZC
1/0 solid al 260 10-#16 8.26 18.47 20.35 25.77 867 254 166 0.68 0.16 223 0.71 0.32 Q9P00ZC
1/0 awg al 260 10-#16 8.59 18.69 20.57 26.00 878 254 166 0.70 0.16 223 0.72 0.31 Q9Q00ZC
2/0 awg al 260 11-#16 9.60 19.71 21.59 27.02 960 254 189 0.55 0.16 252 0.58 0.31 Q9R00ZC
3/0 awg al 260 14-#16 10.82 20.93 22.81 28.23 1081 279 215 0.44 0.15 284 0.47 0.29 Q9S00ZC
4/0 awg al 260 17-#16 12.14 22.25 24.13 29.56 1198 279 244 0.35 0.15 318 0.39 0.28 Q9T00ZC
250 MCM al 260 21-#16 13.28 23.65 25.53 30.95 1408 305 268 0.30 0.14 344 0.34 0.27 Q9U00ZC
350 MCM al 260 27-#16 15.72 26.09 28.42 33.85 1699 330 322 0.21 0.13 400 0.27 0.25 Q9V00ZC
500 MCM al 260 25-#14 18.80 29.16 31.50 37.60 2283 356 389 0.16 0.13 453 0.22 0.23 Q9W00ZC
750 MCM al 260 24-#12 23.11 33.73 36.07 44.44 3131 406 473 0.11 0.12 514 0.18 0.19 Q9X00ZC
1000 MCM al 260 31-#12 26.92 41.96 45.16 53.53 3903 432 535 0.09 0.12 557 0.16 0.16 Q9Y00ZC

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.