General Cable EmPowr® 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation
Select gauge from drop-down menu for prices:
- General Cable EmPowr® 1/0 AWG 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 2/0 AWG 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 3/0 AWG 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 4/0 AWG 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 250kcmil 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 350kcmil 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 500kcmil 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 750kcmil 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
- General Cable EmPowr® 1000kcmil 35 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 345 mils
Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97- 682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable.
Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.
Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer.
Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III.
Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation.
Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator.
Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC).
Features and Benefits:
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Flexibility for easy handling
• Excellent moisture resistance
• Deformation-resistant
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield without the use of a release agent
• Sunlight-resistant
Temperature Rating:
• Normal - 105°C
• Emergency* - 140°C
• Short Circuit - 250°C
Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.
Options:
• Copper conductors
• EmPowr® Fill LF Lead-Free EAM
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• Dry nitrogen cure
• True Triple Extrusion
• 3 X 1/C triplex or parallel
• Type MV-105 UL 1072
• UL Listedb
compressed conductor | copper neutral | approx. weight (1) lb/1000 ft | ampacity (2) | Action |
al awg/ kcmil | wire size awg | total | in duct | |
1/0 | 22 | 784 | 170 | Request a Quote |
2/0 | 22 | 845 | 190 | Request a Quote |
3/0 | 22 | 918 | 220 | Request a Quote |
4/0 | 22 | 1007 | 250 | Request a Quote |
250 | 22 | 1088 | 275 | Request a Quote |
350 | 22 | 1268 | 340 | Request a Quote |
500 | 20 | 1615 | 410 | Request a Quote |
750 | 20 | 2017 | 525 | Request a Quote |
1000 | 20 | 2385 | 615 | Request a Quote |