Belden 16 AWG CSA Instrumentation 600V ACIC Armored Individually and Overall Beldfoil Shielded Pairs 7x24 Cable
Select gauge from drop-down menu for prices:
- Belden 25504 16 AWG 1 Pair 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25510 16 AWG 2 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25511 16 AWG 4 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25512 16 AWG 6 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25513 16 AWG 8 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25518 16 AWG 12 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 25519 16 AWG 24 Pairs 600V ACIC Armored Multi Conductor Steel Cable
- Belden 24500 16 AWG 1 Pair 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24505 16 AWG 2 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24502 16 AWG 4 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24506 16 AWG 6 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24503 16 AWG 8 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24504 16 AWG 12 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
- Belden 24510 16 AWG 24 Pairs 600V ACIC Armored Multi Conductor Aluminum Cable
Product Details
Suitable for use in 300V, 600V or some 1000V environments, Belden offers a complete line of unarmored CSA-rated control, instrumentation and power cables.
Combined with a wide range of conductor, insulation and jacket options, Belden has the right cable solution to fit your needs.
Benefits:
• Eliminates the need for costly conduit or burial piping
• Provides superior mechanical protection for use in underground or hazardous environments
• Resists sunlight, chemicals and oil for long-life performance
Features:
• Designed specifically to meet CSA22.2 Type CIC standard
• Wide range of conductor and pair counts
• Armored options available
Insulation:
• Material: PVC - Polyvinyl Chloride
• Wall Thickness (mm): 0.762
Inner Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 8.636
• Inner Jacket Ripcord: Yes
Outer Shield Drain Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 16.256
• Outer Jacket Ripcord: Yes
Armor:
• Armor Type: Interlocked
• Armor Material: Aluminum
Overall Cable:
• Separator Material: Polyester
Mechanical Charactertistics (Overall):
• Installation Temperature Range: -25°C To +105°C
• Wet Temperature Range: -40°C To +75°C
• Dry Temperature Range: -40°C To +105°C
• Bulk Cable Weight: 254.482 Kg/Km
• Max. Recommended Pulling Tension: 418.131 N
• Min. Bend Radius/Minor Axis: 195.580 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CSA Specification: C22.2#239, Type ACIC, C22.2#174, HLABCD, C22.2#0.3, Clause 4.31 Low Acid Test
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
• Other Specification: Low Acid Test
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 13.7802 (16 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 48.2307 (22 AWG)
• Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: 21.983 Ohm/km
• Max. Operating Voltage - Other: 600 (CEC ACIC)
Flame Test:
• CSA Flame Test: FT4
Suitability:
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
awg | # pairs | belden cable part number |
Action | ||
al. | steel | aluminum | steel | ||
16 | 16 | 1 | 24500 | 25504 | Request A Quote |
16 | 16 | 2 | 24505 | 25510 | Request A Quote |
16 | 16 | 4 | 24502 | 25511 | Request A Quote |
16 | 16 | 6 | 24506 | 25512 | Request A Quote |
16 | 16 | 8 | 24503 | 25513 | Request A Quote |
16 | 16 | 12 | 24504 | 25518 | Request A Quote |
16 | 16 | 24 | 24510 | 25519 | Request A Quote |