Prysmian Cable 35kV 133% Copper TRXLPE URD CSA Medium Voltage Utility Cables

Prysmian Cable 35kV 133% Copper TRXLPE URD CSA Medium Voltage Utility Cables

Select gauge from drop-down menu for prices:

Prysmian Cable 35kV 133% Copper TRXLPE URD CSA Medium Voltage Utility Cables

Product Details

Conductor: Solid or Class B compact or compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength VOLTENE™ TRXLPE insulation, exhibiting an optimum balance of mechanical and electrical properties, insuring resistance to treeing.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced.

Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes.

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength VOLTALENE™ TRXLPE insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket.

Options:
• Black LLDPE jacket with no stripes
• Black PVC jacket sleeved over separator tape
• No Jacket
• EPROTENAX™ (EPR) insulation
• Multiplex cables
• Tinned round and flat strap neutrals
• Strandseal®
• Super smooth conductor shield
• Cables made to AEIC CS8 and/or ICEA S-94-649
• 46kV

Installations:
• Conduit in Air
• Direct Buried
• Underground Duct
• Isolated in Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary

Specifications and Ratings:
• CSA - CSA C68.5 -40°C
• For 90°C continuous, 130°C emergency, 250°C short-circuit operation.

conductor insulation
thickness
(mils)
concentric
neutral
cond.
dia.(in)
ins.
dia.
(in)
ins.
shield
diameter (in)
jacket
dia.(in)
cable
weight
(lbs/kft)
min.
bending
radius (in)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)
prysmian
cable
part
number
(a) (b) (c) (d) 90°c in duct 90°c direct buried
35kv 133% copper single phase - full neutral
1/0 solid cu 420 16-#12 8.26 31.37 33.71 40.66 2086 330 215 0.84 0.12 276 0.84 0.12 QC701ZC
1/0 awg cu 420 16-#12 8.59 31.60 33.93 40.88 2104 330 217 0.85 0.11 278 0.85 0.11 QC801ZC
2/0 awg cu 420 20-#12 9.60 32.61 34.95 41.90 2391 356 248 0.67 0.11 316 0.67 0.11 QC901ZC
3/0 awg cu 420 26-#12 10.82 33.83 36.17 44.54 2857 381 281 0.53 0.10 358 0.53 0.10 QCA01ZC
4/0 awg cu 420 32-#12 12.14 35.15 37.49 45.86 3291 381 319 0.43 0.10 402 0.43 0.10 QCB01ZC
35kv 133% copper three phase - one-third neutral
1/0 solid cu 420 14-#16 8.26 31.37 33.71 39.13 1701 330 216 0.41 0.18 277 0.45 0.32 QC700ZC
1/0 awg cu 420 14-#16 8.59 31.60 33.93 39.36 1718 330 216 0.42 0.17 278 0.46 0.31 QC800ZC
2/0 awg cu 420 17-#16 9.60 32.61 34.95 40.38 1923 330 245 0.34 0.17 311 0.38 0.30 QC900ZC
3/0 awg cu 420 21-#16 10.82 33.83 36.17 41.60 2180 356 278 0.27 0.16 347 0.32 0.29 QCA00ZC
4/0 awg cu 420 27-#16 12.14 35.15 37.49 44.34 2586 356 314 0.22 0.16 383 0.27 0.27 QCB00ZC
250 MCM cu 420 21-#14 13.28 36.55 38.89 46.41 2970 381 344 0.19 0.15 408 0.24 0.26 QCC00ZC
350 MCM cu 420 28-#14 15.72 38.99 42.19 49.71 3745 406 408 0.14 0.15 461 0.20 0.23 QCD00ZC
500 MCM cu 420 26-#12 18.77 42.04 45.24 53.61 4898 432 480 0.11 0.14 510 0.17 0.19 QCE00ZC
750 MCM cu 420 25-#10 24.59 48.11 51.31 60.76 6901 508 562 0.08 0.13 572 0.15 0.16 QCF00XC
1000 MCM cu 420 32-#10 28.37 51.89 55.09 64.54 8588 533 612 0.07 0.12 624 0.13 0.13 QCG00XC

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.