Belden 1526A 20 AWG 1 Triad 300V PLTC Cable
Select gauge from drop-down menu for prices:
- Belden 20 AWG Triads 300V PLTC Beldfoil Shielding Orange Communication Cable
- Belden 3017A 20 AWG 2 Triads 300V PLTC Cable
- Belden 3020A 20 AWG 4 Triads 300V PLTC Cable
- Belden 3021A 20 AWG 8 Triads 300V PLTC Cable
- Belden 3022A 20 AWG 12 Triads 300V PLTC Cable
- Belden 3023A 20 AWG 16 Triads 300V PLTC Cable
- Belden 3024A 20 AWG 24 Triads 300V PLTC Cable
Description:
• 20 AWG triads stranded (7x28) bare copper conductors, twisted triads, PVC insulation, overall Beldfoil
shield (100% coverage), PVC Jacket.
Insulation:
• Material: PVC - Polyvinyl Chloride
• Dia. (mm): 1.7272
Outer Shield Drian Wire AWG:
• AWG: 22
• Stranding: 7x30
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.9398
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• UL Temperature Rating: 105°C
• Bulk Cable Weight: 32 lbs/1000 ft.
• Max. Recommended Pulling Tension: 42 lbs.
• Min. Bend Radius/Minor Axis: 2.200 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, ITC-ER, PLTC-ER
• CEC/C(UL) Specification: CMG
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Inductance (?H/ft): 0.19
• Nom. Capacitance Conductor to Shield (pF/ft): 55
• Nom. Capacitance Conductor to Conductor (pF/ft): 30
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 9.5
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 6.5
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 4.8 Amps/Conductor @ 25°C
Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• C(UL) Flame Test: FT4
• IEEE Flame Test: 1202
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 20 |
# triads | 1 |
stranding | 7x28 |
no. of conductors | 2 |
conductor material | bare copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 5.563 |
belden cable part number | 1526A |