Belden® paired cable products are manufactured in a variety of gage sizes, dimensions, insulation materials, shielding configurations, and jacketing materials including Plenum and High-Temperature versions to meet the technical requirements of many different types of systems.

Paired cables allow balanced signal transmission, which results in lower crosstalk through common mode rejection. Due to the improved noise immunity of twisted pairs, they generally permit higher data speeds than multi-conductor cables.

Insulation:
• Material: FEP - Fluorinated Ethylene Propylene
• Wall Thickness (mm): 0.1524

Outer Shield Drain Wire AWG:
• AWG: 24
• Stranding: 7x32
• Material: TC - Tinned Copper

Outer Jacket:
• Trade Name: Flamarrest®
• Material: LS PVC - Low Smoke Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.381

Mechanical Charactertistics (Overall):
• Operating Temperature Range: 0°C To +60°C
• Bulk Cable Weight: 56 lbs/1000 ft.
• Max. Recommended Pulling Tension: 143 lbs.
• Min. Bend Radius/Minor Axis: 3 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMP
• CEC/C(UL) Specification: CMP
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Inductance (µH/ft): 0.17
• Nom. Capacitance Conductor to Conductor (pF/ft): 23
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/ft): 42
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 15
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 1.5 Amps/Conductor @ 25°C

Flame Test:
• UL Flame Test: NFPA 262
• CSA Flame Test: FT6

Plenum/Non-Plenum:
• Plenum (Y/N): Yes

awg # pairs overall cable-
nominal
dia. (mm)
belden cable
part
number
Action
24 12 7.061 82512 Request A Quote