Prysmian and Draka Cable RFOU-HCF 6/10 (12) kV P30 HydroCarbon Fire resistant, Flame Retardant Halogen-free Instrumentation Cable

Prysmian and Draka Cable RFOU-HCF 6/10 (12) kV P30 HydroCarbon Fire resistant, Flame Retardant Halogen-free Instrumentation Cable

Select gauge from drop-down menu for prices:

Prysmian and Draka Cable RFOU-HCF 6/10 (12) kV P30 HydroCarbon Fire resistant, Flame Retardant Halogen-free Instrumentation Cable
Prysmian and Draka Cable RFOU-HCF 6/10 (12) kV P30 HydroCarbon Fire resistant, Flame Retardant Halogen-free Instrumentation Cable

Conductor: Tinned stranded and compressed copper (STCC), IEC 60228 class 2

Conductor Screen Semiconductive: Semiconductive layer (EP-rubber)

Insulation: EP-rubber, IEC 60092-360 (EPR)

Insulation Screen Semiconductive: Semiconductive layer (EP-rubber)

Lay up / Shielding: Cores laid up together. Cores are identified by Brown, Black or Grey threads under and over the metallic screen on each conductor.

Inner Covering: Flame retardant and halogen-free thermoset compound

Tape Over Bedding: PET tape

Armour/Screen: Tinned copper wire braid

Tape Over Armour/Screen: PET tape

Outer Sheath: Flame retardant, halogen-free and mud resistant thermoset compound, SHF2 (IEC 60092-360)

HCF protection : Extruded heatblock compound

Tape: Lapped glassfibre tape

Outer Sheath: Flame retardant, halogen-free and thermoplastic compound, SHF 1 (IEC 60092-360)

Marking Text: E.g. "meter" "year" DRAKA NORSK KABLE RFOU-HCF 6/10(12) kV P 30 1 70/16 MM2 HCF 1100/60 FLEX-FLAME

Outer Sheath Colour: Red

Operating Temperature: 90°C

Operating Voltage: 6/10(12) kV

Standards Applied:
• IEC 60092-354 - Design
• Draka Norsk Kable-HCF protection
• IEC 60228 class 2 - Conductor
• IEC 60092-360 - Insulation
• IEC 60092-360 - Sheath
• IEC 60332-1-2 - Flame Retardant
• IEC 60332-3-22 - Fire retardant
• EN 1363-2 / ISO 834- HC fire resistance
• IEC 60754-1,2 - Halogen Free
• IEC 61034-1,2 - Low Smoke

Application: Fixed installation for medium voltage (MV) power in both EX - and safe areas, emergency and critical system where requirement for fire resistance is vital.

Range and Dimensions
Type [mm²] Diameter over
Bendding [mm]
Weight of
cable approx. [kg/km]
Prysmian and
Draka Cable
Part Number
action
1×70/16 23.5 ±1.5 5220 886498 Request A Quote
1×95/16 25.5 ±1.5 5900 886795 Request A Quote
1×120/20 27.5 ±1.5 6340 887247 Request A Quote
1×150/19 28.5 ±1.5 6670 Request A Quote
1×185/18 30.5±1.5 7320 887182 Request A Quote
1×240/21 33.0 ±1.5 8250 Request A Quote
1×300/29 35.0 ±1.5 9280 Request A Quote
3× 50/31 47.0±2.0 10970 Request A Quote