Lapp OLFLEX® VFD 2XL with Signal 600V UL TC-ER Flexible Cable
Select gauge from drop-down menu for prices:
- Lapp 700710 16 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700711 14 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700712 12 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700713 10 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700714 8 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700715 6 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700716 4 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
- Lapp 700717 2 AWG 4C OLFLEX VFD 2XL with Signal Flexible UL TC-ER Approved Cable
ÖLFLEX® VFD 2XL with Signal is a robust oil- and UV-resistant shielded motor cable for VFD drives, with a pair for brake or temperature sensor. The XLPE (plus) insulation with enhanced electrical properties can withstand twice the dielectric voltage test, provides extended performance, and is suitable for 2kV applications.
Construction
Conductors:
• Finely stranded bare copper
Insulation:
• XLPE (plus)
Shielding:
• barrier tape; triple layer foil tape (100% coverage)tinned copper braid (85% coverage)
Jacket:
• specially formulated thermoplastic elastomer (TPE) black
Technical data
Minimum bend radius:
• 7.5 x cable diameter
Temperature range:
• - UL/CSA TC: -25°C to +90°C
• - for stationary use: -40°C to +105°C
• - for flexible use: -25°C to +105°C
Nominal voltage:
• - UL TC: 600V/2000V
• - UL Flexible Motor Supply: 1000V
• - c(UL) CIC/TC: 600V
•- cRU AWM: 1000V
Test voltage:
• 6000V
Conductor stranding:
• - 16 - 6 AWG: Class 5 fine wire
• - 4 - 2 AWG: Class K fine wire
Color code:
• black with white numbers, plus green/yellow ground and one black pair with white numbers
Approvals:
• UL: UL: TC-ER per UL 1277
• Attributes: UL Oil Res I/II
90°C wet or dry
-40°C cold bend; -25°C cold impact
sunlight resistant
direct burial
NFPA 79
bus drop approval
• NEC: Class 1 Division 2 per NEC Article 501
• Canada: c(UL) CIC/TC FT4
cRU AWM I/II A/B FT4
• Additional: CCE (50V - 1kV) & RoHS
Features
• One cable for applications up to 2kV
• Low capacitance design
• Industrial grade phthalate-free jacket designed for harsh environments.
• UL TC-ER & c(UL) CIC/TC approved
• Reduces space and weight in tray
•No conduit required due to TC-ER rating
AWG | Number of conductors | Nominal Outer Diameter |
Copper Weight (lbs/mft) |
Approx. Weight (lbs/mft) |
Part Number | |
inches | mm | |||||
16 AWG (1.5 mm²) | ||||||
16 | 4 + (18 AWG) | 0.652 | 16.6 | 91 | 200 | 700710 |
14 AWG (2.5 mm²) | ||||||
14 | 4 + (18 AWG) | 0.687 | 17.4 | 132 | 252 | 700711 |
12 AWG (4 mm²) | ||||||
12 | 4 + (18 AWG) | 0.752 | 19.1 | 160 | 294 | 700712 |
10 AWG (6 mm²) | ||||||
10 | 4 + (18 AWG) | 0.798 | 20.3 | 215 | 354 | 700713 |
8 AWG (10 mm²) | ||||||
8 | 4 + (18 AWG) | 0.986 | 25.0 | 334 | 690 | 700714 |
6 AWG (16 mm²) | ||||||
6 | 4 + (18 AWG) | 1.112 | 28.2 | 504 | 905 | 700715 |
4 AWG (21 mm²) | ||||||
4 | 4 + (18 AWG) | 1.259 | 32.0 | 667 | 1125 | 700716 |
2 AWG (33.7 mm²) | ||||||
2 | 4 + (18 AWG) | 1.403 | 35.6 | 1027 | 1580 | 700717 |
( ) = shielded pair