Seacoast Types TXT, TXTA, TXTB Three Conductor XLP Insulation 600 Volts Cable

Seacoast Types TXT, TXTA, TXTB Three Conductor XLP Insulation 600 Volts Cable

Product Details

Three (3) conductor, 600 Volts, stranded bare copper, Cross-Linked Polyethylene (XLP) insulation, color coded in accordance with IEEE Std. 45, fillers where necessary, binder tape as required, moisture resistant PVC jacket, braided metal armor (optional). Flame retardant – meets IEEE 1202/UL 1685 flame test. Type: TXTA with Aluminum Armor, type: TXTB with Bronze Armor.

size
approx.
awg.
equiv.
type
&
size
armored cable
approx. weight
lbs/1000 ft
ampacity
@ 45°c
ambient
Action
bronze 90° c
rating
14 txt-4 210 24 Request A Quote
12 txt-6 265 29 Request A Quote
10 txt-10 340 38 Request A Quote
8 txt-16 480 48 Request A Quote
6 txt-26 665 65 Request A Quote
4 txt-41 905 83 Request A Quote
2 txt-66 1210 111 Request A Quote
1 txt-83 1498 131 Request A Quote
1/0 txt-106 1790 150 Request A Quote
2/0 txt-133 1960 173 Request A Quote
3/0 txt-168 2230 201 Request A Quote
4/0 txt-212 2850 232 Request A Quote
250 mcm txt-250 3445 259 Request A Quote
300 mcm txt-300 4015 290 Request A Quote
350 mcm txt-350 4546 317 Request A Quote
400 mcm txt-400 5109 342 Request A Quote
500 mcm txt-500 6160 393 Request A Quote

QUESTIONS & ANSWERS