Belden Cable Interbus-S Cable

Belden Cable Interbus-S Cable

Product Details

Interbus-S is a serial bus, master/slave fieldbus communication system developed by Phoenix Contact to transmit data between control systems (PCs, PLCs, VMEbus computers, robot controllers, etc.) and distributed I/O modules which communicate with sensors and actuators/switches.

Interbus-S Remote Bus cable contains three twisted-pairs with a single, common shield for communications only, no power. Installation Remote Bus cable is similar to Remote Bus cable, except that it contains three additional conductors for supplying communications power (up to 4.5 amps) to various devices.

Insulation:
• Material: PE - Polyethylene (24 AWG) And PVC - Polyvinyl Chloride (18 AWG)

Outer Shield Drain Wire AWG:
• AWG: 24
• Stranding: 7x32
• Conductor Material: TC - Tinned Copper
• Diameter: 0.024

Outer Jacket:
• Material: PUR - Polyurethane

Mechnical Characteristics (Overall):
• Operating Temperature Range: -40°C To +80°C
• UL Temperature Rating: 80°C (UL AWM Style 20233)
• Bulk Cable Weight: 62 lbs/1000 ft.
• Max. Recommended Pulling Tension: 100 lbs.
• Min. Bend Radius/Minor Axis: 3 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards & Environmental Programs:
• AWM Specification: UL Style 20233 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire & Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Characteristic Impedance (Ohm): 100
• Nom. Capacitance Conductor Shield (pF/ft): 15.4
• Nominal Velocity of Propagation VP (%): 66 (24 AWG)
• Nominal Delay (ns/ft): 1.6
• Nom. Conductor DCR @ 20°C (Ohm/1000 ft): 23.4 (24 AWG) and 6.6 (18 AWG)
• Nom. Outer Shield DCR @ 20°C (Ohm/1000 ft): 2.7
• Max.Operating - UL: 300 V RMS (UL AWM Style 20233)
• Max. Recommended Current: 2.1 (24 AWG) and 4.8 (18 AWG)

Suitability:
• Sunlight Resistance: High

Plenum/Non-Plenum:
• Plenum (Y/N): No

Benefits:
• Easy installation and start up
• Increased space savings
• High efficiency

Features:
• Automatic configuration capability
• Protocol chips in fieldbus technology
• Low protocol overhead

awg # pairs overall cable -
nominal dia. (in.)
belden cable
part number
Action
24 and 18 3 0.024 3119A Request A Quote
24 3 0.277 3120A Request A Quote

QUESTIONS & ANSWERS