General Cable Low-Smoke Zero-Halogen® 150V Profibus Cable One Pair Overall Shielded Armored Sheathed ABS Type Approved ETL Confirmed
Select gauge from drop-down menu for prices:
Conductor: 22 AWG solid tinned copper: .025" nom. O.D.
Insulation: Foam Polyethylene, .040" nom. wall: .106" nom. O.D.
Pair:
• Two insulated conductors twisted together
• Color Code: C1: Red C2: Green
Inner Shield: Aluminum/Polyester tape with 25% overlap 100% coverage (aluminum side out)
Drain Wire: 22 AWG solid tinned copper spirally applied
Overall Shield: 34 AWG tinned copper braid, 90% min. coverage
Inner Sheath: Low-Smoke, Zero-Halogen Polyolefin — .035" nom. wall, Black: .315" nom. O.D.
Armor: 28 AWG bronze braid, 88% min. coverage
Outer Sheath: Low-Smoke, Zero-Halogen Polyolefin, .045" nom. wall, Black: .470" nom. O.D.
Cable Weight: 150 lbs/kft nom.
Features:
• Mechanically enhanced construction renders the cable suitable for installation in cable tray as an interconnect cable
• Suitable for installation in vessels’ quarters area
Compliances:
• Flammability: IEC 60332-3-22 Category A
• Smoke: IEC 61034-1 & -2, MIL-DTL-24643B and NES 711
• Halogen Content: IEC 60754-1 & -2
• Toxicity: MIL-DTL-24643B and NES 713
• Acidity: IEC 60754-1 & -2 and MIL-DTL-24643B
• Armor: IEEE 1580 and IEC 60092-350
Third-Party Testing:
ETL has tested and confirmed that this product complies with the above specifications
(report number 3116259CRT-006)
Electrical Characteristics
Conductor DCR: 16.5 V/kft nom.
Capacitance: 8.8 pF/ft nom.
Impedance: 150 ± 15 V
Temperature & Voltage Ratings: -30°C to +75°C/300 V Max.
Velocity of Propagation: 78% nom.
Attenuation (Nom.):
freq.(mhz) | db/100 ft |
0.2 | 0.27 |
4.0 | 0.67 |
16.0 | 1.37 |
100.0 | 3.75 |
300.0 | 6.52 |
General Cable Part number: EO22P0011203