General Cable EmPowr® 25 kV Longitudinally Applied Corrugated Tape LLDPE Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

General Cable EmPowr® 25 kV Longitudinally Applied Corrugated Tape LLDPE Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Select gauge from drop-down menu for prices:

General Cable EmPowr® 25 kV Longitudinally Applied Corrugated Tape LLDPE Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Product Details

Complete Cable: Lead-free cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Corrugated copper tape and an extruded black jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Tree-Retardant Crosslinked Polyethylene (TRXLPE) insulated shielded power cable.

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.

Conductor Shield: Extruded lead-free semi-conducting thermosetting polymeric stress control layer.

Insulation: Extruded unfilled lead-free Tree-Retardant Cross-linked Polyethylene (TRXLPE).

Insulation Shield: Extruded lead-free semi-conducting thermosetting layer, clean and free stripping from insulation.

Longitudinally Applied Corrugated Tape: Copper, 8 or 10 mil thick Longitudinally Applied Corrugated Tape (LACT) with a minimum 375 mil overlap.

Jacket: Black, non-conducting, sunlight-resistant Linear Low-Density Polyethylene (LLDPE).

Features and Benefits:
• Lead-free environmentally friendly cable
• Even distribution of fault current and better heat dissipation
• Allows expansion/contraction of the cable core
• Improved bending characteristics versus helical copper tape shield
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Excellent moisture resistance
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield
• Sunlight-resistant

Temperature Rating:
• Normal - 90°C
• Emergency* - 130°C
• Short Circuit - 250°C

Applications: EmPowr® Link+ cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.

Options:
• Copper conductors
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• BIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT
• TRIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT 3. sealed overlap and blocked LACT/jacket
• Sealed LACT overlap
• True Triple Extrusion
• Low-strip insulation shield
• Red stripes on jacket
• Semi-conducting thermoplastic jacket
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• TRXLPE Class III insulation for 105°/140°C temperature rating
• UL Listed

longitudinally applied corrugated tape shielded power cable
compressed
conductor
ampacity (2) Action
al awg or kcmil no. of wires direct buried in duct
250 37 370 285 Request a Quote
250 37 370 285 Request a Quote
350 37 445 345 Request a Quote
350 37 445 345 Request a Quote
500 37 545 425 Request a Quote
500 37 545 425 Request a Quote
750 61 665 530 Request a Quote
750 61 665 530 Request a Quote
1000 61 780 630 Request a Quote
1000 61 780 630 Request a Quote