Conductors: Solid or Class B Compressed concentric strand Aluminum alloy 1350 or soft drawn annealed copper per ASTM. 

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation. 

Insulation: Natural high dielectric strength EPROTENAX™ EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life. 

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping. 

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced. 

Jacket: Black, insulating, sunlight resistant, linear low density polyethylene encapsulating the neutral wires with three extruded red stripes and NESC lightning bolt symbol. 

Description: Single conductor cable with aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, black encapsulating linear low-density polyethylene (LLDPE) jacket. 

Options: 
• Black LLDPE jacket with no stripes 
• Black PVC jacket sleeved over separator tape 
• No Jacket 
• Multiplex cables 
• Tinned round and flat strap neutrals 
• Strandseal® 
• Compact stranded conductors 
• UL MV-90 Rating if required 
• 46kV 
• RUS - Bulletin 1728F-U1 

Installation: 
• Conduit in Air 
• Underground Duct 
• Wet Locations 
• With Messenger 
• Direct Buried 
• Isolated in Air 
• Dry Locations 
• Utility Primary 

Specifications and ratings:
• AEIC- AEIC CS8 
• ICEA- ICEA S-94-649 
• For 105°C continuous, 140°C emergency, 250°C short-circuit operation.

conductor insulation
thickness
(mils)
concentric
neutral
cond.
dia.(in)
ins.
dia.
(in)
ins.
shield
diameter (in)
jacket
dia.(in)
cable
weight
(lbs/kft)
min.
bending
radius (in)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)

amp.
(amps)
+/- sequence
imp.
resistance
(µΩ/ft)
+/- sequence
imp.
reactance
(µΩ/ft)
prysmian Cable
part
number
(a) (b) (c) (d) 105°c in duct 105°c direct buried
35kv 133% copper single phase - full neutral
1/0 solid cu 420 16-#12 0.325 1.22 1.31 1.58 1498 13 234 268 36 298 268 36 QR7010A
1/0 awg cu 420 16-#12 0.364 1.26 1.35 1.62 1542 13 236 270 34 300 270 34 QR8010A
2/0 awg cu 420 13-#10 0.408 1.30 1.39 1.77 1865 15 270 212 33 270 212 33 QR9010A
3/0 awg cu 420 16-#10 0.458 1.35 1.44 1.82 2111 15 306 170 31 386 170 31 QRA010A
4/0 awg cu 420 16-#9 0.515 1.41 1.50 1.90 2457 16 348 136 30 434 136 30 QRB010A
35kv 133% copper three phase - one third neutral
1/0 solid cu 420 9-#14 0.325 1.22 1.31 1.55 1272 13 235 132 54 299 142 97 QR7000A
1/0 awg cu 420 9-#14 0.364 1.26 1.35 1.59 1314 13 235 134 53 300 144 95 QR8000A
2/0 awg cu 420 11-#14 0.408 1.30 1.39 1.63 1463 14 267 107 51 337 119 92 QR9000A
3/0 awg cu 420 14-#14 0.458 1.35 1.44 1.74 1717 14 302 86 49 376 99 88 QRA000A
4/0 awg cu 420 18-#14 0.515 1.41 1.50 1.80 1954 15 342 69 47 415 85 83 QRB000A
250 mcm cu 420 21-#14 0.561 1.46 1.55 1.85 2167 15 375 59 47 443 76 79 QRC000A
350 mcm cu 420 18-#12 0.664 1.57 1.69 2.02 2757 17 445 44 44 501 64 71 QRD000A
500 mcm cu 420 17-#10 0.794 1.70 1.82 2.19 3580 18 525 33 42 557 54 60 QRE000A
750 mcm cu 420 20-#9 0.974 1.88 2.00 2.40 4843 20 616 26 39 624 45 48 QRF000A
1000 mcm cu 420 21-#8 1.124 2.03 2.15 2.58 6073 21 671 23 36 682 39 40 QRG0001A