Prysmian and Draka Cable QFCI-I/O/RM-JM/-F1 Indoor and Outdoor Fire Resistant Flame Retardant Halogen-free Loose Tube Fiber Optic Cable
Select gauge from drop-down menu for prices:
Optical cable for indoor and outdoor use in vital communication and emergency systems that need to be operational during fire. The cable has a patented design that ensures operation for more than 3 hours in fires up to 1000ºC. The cable is halogen free and flame retardant to protect against secondary damage to electronic equipment during and after fire. Outer sheath is made from black UV-stabilized and weather resistant material and may be exposed for shorter periods to fluids such as diesel and mineral oils. The resistance to these fluids is according to IEC60811-2-1. The cable is reinforced with a steel wire braiding. The fibres are protected in jelly filled loose tubes stranded around a central strength member to ensure optimum performance and long life. Each fibre and loose tube is colour coded for easy identification during splicing and termination. The outer sheath is marked to show fibre type and cable type. The sheath colour is BLACK.
Tensile strength (IEC 60794-1-2E1):
• Max tensile load during installation 1500 N
• Max tensile load during operation 500 N
Crush: (IEC 60794-1-2E3) 3000 N/10cm
Impact: (IEC 60794-1-2E4) 30J
Torsion: (IEC 60794-1-2E7) 1 turn/1m
Cable bending:
• Minimum bending diameter 250 mm
• Cable bend (IEC 60794-1-2E11) <0.1dB/ ?5 turn
Temperature window:
• Operation -40?C to +70?C
• Installation -10?C to +70?C
• Storage -40?C to +70?C
Chemical reistance:
• Mineral oils IRM 902 (IEC60811-2-1) - 7 days/23°C, 4 hours/70°C
• Diesel - IRM 903 (IEC60811-2-1) - 7 days/23°C, 4 hours/70°C
Fire and smoke classifications:
• IEC 60331-25 (750?C, 90 minutes) <1.0 dB excess loss
• Upgraded IEC 60331-25 (1000?C, 3 hours) <1.5 dB excess loss
• BP GS 112-2 Clause7.1
• IEC 61034
• IEC 60332-3-22 (Cat. A)
• IEC 60332-3-24 (Cat. C)
• IEC 60754-1
• IEC 60754-2
number of fibres |
number of fibres in each tube |
weight (kg/km) | heat release (mj/km) |
action |
4 | 2 | 260 | 1390 | Request A Quote |
8 | 4 | 260 | 1381 | Request A Quote |
12 | 4 | 260 | 1324 | Request A Quote |
24 | 4 | 260 | 1138 | Request A Quote |
48 | 8 | 260 | 1138 | Request A Quote |