General Cable EmPowr® 5 kV Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

General Cable EmPowr® 5 kV Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Select gauge from drop-down menu for prices:

General Cable EmPowr® 5 kV Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Product Details

Complete Cable: Lead-free cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Tree-Retardant Cross-linked Polyethylene(TRXLPE) insulated shielded power cable.

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.

Conductor Shield: Extruded lead-free semi-conducting thermosetting polymeric stress control layer.

Insulation: Extruded unfilled lead-free Tree-Retardant Cross-linked Polyethylene (TRXLPE).

Insulation Shield: Extruded lead-free semi-conducting thermosetting layer, clean and free stripping from insulation.

Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator.

Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC).

Features and Benefits:
• Lead-free environmentally friendly cable
• Triple-extruded for clean interfaces
• Dry nitrogen cure for enhanced performance
• Class 10,000 environment utilized for cable core material handling
• Excellent moisture resistance
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield
• Sunlight-resistant

Temperature Rating:
• Normal - 90°C
• Emergency* - 130°C
• Short Circuit - 250°C

Applications: EmPowr® Link+ cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.

Options:
• Copper conductors
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• True Triple Extrusion
• UltraPowr® smoother and cleaner semi-conducting conductor shield
• Low-strip insulation shield
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• TRXLPE Class III insulation for 105°/140°C temperature rating
• Type MV-105 UL 1072
• UL Listed

copper wire shielded power cable
compressed
conductor
copper
neutral
diameter (1)
inches
nominal
jacket
thkn.
inches
(1)
approx. weight (1)
lb/1000 ft
ampacity (2)
al
awg or
kcmil
no.
of
wires
no.
of
wires
wire
size
awg
insulation pvc
jacket
al
cond.
cu
wires
total direct
buried
in
duct
min. max.
115 mils NOMINAL TRXLPE INSULATION – 5 kV 133% OR 8 kV 100%
2 7 9 24 0.525 0.605 0.787 0.065 62 12 267 165 125
1 19 6 22 0.565 0.645 0.837 0.065 78 13 296 190 145
1/0 19 7 22 0.605 0.685 0.907 0.065 99 15 358 215 165
2/0 19 7 22 0.650 0.725 0.951 0.080 125 15 401 245 185
3/0 19 7 22 0.700 0.775 1.001 0.080 158 15 454 280 215
4/0 19 8 22 0.755 0.835 1.057 0.080 199 17 519 320 245
250 37 8 22 0.810 0.890 1.113 0.080 234 17 607 355 275
350 37 9 22 0.905 0.980 1.216 0.080 329 19 717 430 335
500 37 6 20 1.040 1.120 1.357 0.080 468 20 911 525 410
750 61 7 20 1.230 1.310 1.544 0.080 703 23 1228 660 510
1000 61 8 20 1.375 1.460 1.693 0.080 937 27 1527 765 615