Belden Cable 18 AWG Audio Control and Instrumentation Overall Beldfoil Shield Non Plenum Cable

Belden Cable 18 AWG Audio Control and Instrumentation Overall Beldfoil Shield Non Plenum Cable

Product Details

Description:
• 18 AWG stranded (16x30) tinned copper conductors, conductors cabled, polyethylene insulation, overall Beldfoil® shield (100% coverage), 20 AWG stranded tinned copper drain wire, PVC jacket.

Insulation:
• Material: PE - Polyethylene
• Wall Thickness (mm): 0.4572

Outer Shield Drain Wire AWG:
• AWG: 20
• Stranding: Stranded
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.8382

Overall Cabling Lay Length and Direction:
• Length (in.): 2.700
• Twists (twist/ft): 4.400 (Left Hand Direction)

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -20°C To +60°C
• UL Temperature Rating: 60°C (UL AWM Style 2093)
• Bulk Cable Weight: 36 lbs/1000 ft.
• Max. Recommended Pulling Tension: 74 lbs.
• Min. Bend Radius/Minor Axis: 2.500 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CM
• NEC Articles: 800
• CEC/C(UL) Specification: CM
• AWM Specification: UL Style 2093 (300 V 60°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Characteristic Impedance (Ohm): 69
• Nom. Inductance (µH/ft): 0.180
• Nom. Capacitance Conductor to Conductor (pF/ft): 24
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/ft): 48
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 6.6
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 8.5
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 5.3 Amps/Conductor @ 25°C ambient (10C Temp. Rise)

Flame Test:
• UL Flame Test: UL1685 UL Loading
• CSA Flame Test: FT1

Suitability:
• Suitability - Indoor: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No
• Plenum Number: 88770

awg # conductors overall cable-
nominal
dia. (mm)
belden cable
part
number
Action
18 3 6.2484 8770 Request A Quote
18 4 6.223 9418 Request A Quote
18 3 3.937 88770 Request A Quote
18 4 4.394 89418 Request A Quote
18 4 4.369 82418 Request A Quote