General Cable EmPowr® 15 kV Longitudinally Applied Corrugated Tape LLDPE Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation
Select gauge from drop-down menu for prices:
- General Cable EmPowr® 175Miles 250MCM 15 kV Longitudinally Applied Corrugated Tape 1.264 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 250MCM 15 kV Longitudinally Applied Corrugated Tape 1.270 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 350MCM 15 kV Longitudinally Applied Corrugated Tape 1.373 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 350MCM 15 kV Longitudinally Applied Corrugated Tape 1.367 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 500MCM 15 kV Longitudinally Applied Corrugated Tape 1.495 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 500MCM 15 kV Longitudinally Applied Corrugated Tape 1.515 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 750MCM 15 kV Longitudinally Applied Corrugated Tape 1.696 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 750MCM 15 kV Longitudinally Applied Corrugated Tape 1.702 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.905 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 250MCM 15 kV Longitudinally Applied Corrugated Tape 1.354 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 250MCM 15 kV Longitudinally Applied Corrugated Tape 1.360 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 350MCM 15 kV Longitudinally Applied Corrugated Tape 1.457 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 350MCM 15 kV Longitudinally Applied Corrugated Tape 1.463 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 500MCM 15 kV Longitudinally Applied Corrugated Tape 1.599 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 500MCM 15 kV Longitudinally Applied Corrugated Tape 1.605 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 750MCM 15 kV Longitudinally Applied Corrugated Tape 1.852 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 750MCM 15 kV Longitudinally Applied Corrugated Tape 1.846 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.995 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
- General Cable EmPowr® 220Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 2.001 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
Product Details
Complete Cable: Lead-free cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Corrugated copper tape and an extruded black jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Tree-Retardant Crosslinked Polyethylene (TRXLPE) insulated shielded power cable.
Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.
Conductor Shield: Extruded lead-free semi-conducting thermosetting polymeric stress control layer.
Insulation: Extruded unfilled lead-free Tree-Retardant Cross-linked Polyethylene (TRXLPE).
Insulation Shield: Extruded lead-free semi-conducting thermosetting layer, clean and free stripping from insulation.
Longitudinally Applied Corrugated Tape: Copper, 8 or 10 mil thick Longitudinally Applied Corrugated Tape (LACT) with a minimum 375 mil overlap.
Jacket: Black, non-conducting, sunlight-resistant Linear Low-Density Polyethylene (LLDPE).
Features and Benefits:
• Lead-free environmentally friendly cable
• Even distribution of fault current and better heat dissipation
• Allows expansion/contraction of the cable core
• Improved bending characteristics versus helical copper tape shield
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Excellent moisture resistance
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield
• Sunlight-resistant
Temperature Rating:
• Normal - 90°C
• Emergency* - 130°C
• Short Circuit - 250°C
Applications: EmPowr® Link+ cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.
Options:
• Copper conductors
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• BIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT
• TRIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT 3. sealed overlap and blocked LACT/jacket
• Sealed LACT overlap
• True Triple Extrusion
• Low-strip insulation shield
• Red stripes on jacket
• Semi-conducting thermoplastic jacket
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• TRXLPE Class III insulation for 105°/140°C temperature rating
• UL Listed
longitudinally applied corrugated tape shielded power cable | ||||||||||||
compressed conductor |
diameter (1) inches |
nominal jacket thkn. inches (1) |
approx. weight (1) lb/1000 ft |
ampacity (2) | ||||||||
al awg or kcmil |
no. of wires |
insulation | lact shield | lldpe jacket |
al cond. |
cu shield |
total | direct buried |
in duct |
|||
min. | max. | thkn. | o.d. | |||||||||
175 mils nominal trxpe insulation – 15 kv 100% insulation level | ||||||||||||
250 | 37 | 0.920 | 1.005 | 0.008 | 1.104 | 1.264 | 0.080 | 234 | 131 | 814 | 370 | 285 |
250 | 37 | 0.920 | 1.005 | 0.010 | 1.110 | 1.270 | 0.080 | 234 | 164 | 848 | 370 | 285 |
350 | 37 | 1.015 | 1.100 | 0.008 | 1.207 | 1.367 | 0.080 | 329 | 157 | 984 | 445 | 345 |
350 | 37 | 1.015 | 1.100 | 0.010 | 1.213 | 1.373 | 0.080 | 329 | 191 | 1020 | 445 | 345 |
500 | 37 | 1.150 | 1.235 | 0.008 | 1.335 | 1.495 | 0.080 | 468 | 157 | 1190 | 545 | 425 |
500 | 37 | 1.150 | 1.235 | 0.010 | 1.355 | 1.495 | 0.080 | 468 | 220 | 1263 | 545 | 425 |
750 | 61 | 1.340 | 1.425 | 0.008 | 1.536 | 1.696 | 0.080 | 703 | 199 | 1574 | 665 | 530 |
750 | 61 | 1.340 | 1.425 | 0.010 | 1.542 | 1.702 | 0.080 | 703 | 243 | 1620 | 665 | 530 |
1000 | 61 | 1.485 | 1.575 | 0.008 | 1.685 | 1.905 | 0.110 | 937 | 208 | 1996 | 780 | 630 |
1000 | 61 | 1.485 | 1.575 | 0.010 | 1.691 | 1.911 | 0.110 | 937 | 260 | 2050 | 780 | 630 |
220 mils nominal trxpe insulation – 15 kv 133% insulation level | ||||||||||||
250 | 37 | 1.010 | 1.100 | 0.008 | 1.194 | 1.354 | 0.080 | 234 | 140 | 899 | 370 | 285 |
250 | 37 | 1.010 | 1.100 | 0.010 | 1.200 | 1.360 | 0.080 | 234 | 191 | 950 | 370 | 285 |
350 | 37 | 1.105 | 1.190 | 0.008 | 1.297 | 1.457 | 0.080 | 329 | 157 | 1068 | 445 | 345 |
350 | 37 | 1.105 | 1.190 | 0.010 | 1.303 | 1.463 | 0.080 | 329 | 191 | 1103 | 445 | 345 |
500 | 37 | 1.240 | 1.330 | 0.008 | 1.439 | 1.599 | 0.080 | 468 | 185 | 1317 | 545 | 425 |
500 | 37 | 1.240 | 1.330 | 0.010 | 1.445 | 1.605 | 0.080 | 468 | 231 | 1365 | 545 | 425 |
750 | 61 | 1.430 | 1.520 | 0.008 | 1.626 | 1.846 | 0.110 | 703 | 203 | 1778 | 665 | 530 |
750 | 61 | 1.430 | 1.520 | 0.010 | 1.632 | 1.852 | 0.110 | 703 | 254 | 1830 | 665 | 530 |
1000 | 61 | 1.575 | 1.670 | 0.008 | 1.775 | 1.995 | 0.110 | 937 | 222 | 2124 | 780 | 630 |
1000 | 61 | 1.575 | 1.670 | 0.010 | 1.781 | 2.001 | 0.110 | 937 | 277 | 2181 | 780 | 630 |