General Cable EmPowr® 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.

General Cable EmPowr® 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.

Select gauge from drop-down menu for prices:

General Cable EmPowr® 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.
EmPowr 175Miles 1000MCM 15 kV Longitudinally Applied Corrugated Tape 1.911 LLDPE Jacket Link and Shielded Power Cable Al Cond. TRXLPE Ins.

Complete Cable: Lead-free cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Corrugated copper tape and an extruded black jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Tree-Retardant Crosslinked Polyethylene (TRXLPE) insulated shielded power cable.

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.

Conductor Shield: Extruded lead-free semi-conducting thermosetting polymeric stress control layer.

Insulation: Extruded unfilled lead-free Tree-Retardant Cross-linked Polyethylene (TRXLPE).

Insulation Shield: Extruded lead-free semi-conducting thermosetting layer, clean and free stripping from insulation.

Longitudinally Applied Corrugated Tape: Copper, 8 or 10 mil thick Longitudinally Applied Corrugated Tape (LACT) with a minimum 375 mil overlap.

Jacket: Black, non-conducting, sunlight-resistant Linear Low-Density Polyethylene (LLDPE).

Features and Benefits:
• Lead-free environmentally friendly cable
• Even distribution of fault current and better heat dissipation
• Allows expansion/contraction of the cable core
• Improved bending characteristics versus helical copper tape shield
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Excellent moisture resistance
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield
• Sunlight-resistant

Temperature Rating:
• Normal - 90°C
• Emergency* - 130°C
• Short Circuit - 250°C

Applications: EmPowr® Link+ cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.

Options:
• Copper conductors
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• BIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT
• TRIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT 3. sealed overlap and blocked LACT/jacket
• Sealed LACT overlap
• True Triple Extrusion
• Low-strip insulation shield
• Red stripes on jacket
• Semi-conducting thermoplastic jacket
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• TRXLPE Class III insulation for 105°/140°C temperature rating
• UL Listed

technical specifications:
compressed conductor (al awg or kcmil) 1000
compressed conductor (no. of wires) 61
diameter (1) inches (min. insulation) 1.485
diameter (1) inches (max. insulation) 1.575
diameter (1) inches (lact shield - thkn.) 0.010
diameter (1) inches (lact shield - o.d.) 1.691
diameter (1) inches (lldpe jacket) 1.911
nominal jacket thkn. inches(1) 0.110
approx. weight (1) lb/1000 ft (al cond) 937
pprox. weight (1) lb/1000 ft (cu shield)
260
approx. weight (1) lb/1000 ft (total) 2050
ampacity (2) (direct buried) 780
ampacity (2) (in duct) 630