14/30 XHHW Tray Cable

14/30 XHHW Tray Cable

Select gauge from drop-down menu for prices:

14/30 XHHW Tray Cable

Product Details

Technical Specifications:
Name: XHHW 14 Gauge
Number of Conductors in Cable: 30
Size AWG: 14
Diameter Complete Cable (O.D.) (Inches): 1.039
Weight Per 1000ft Total (Lbs.): 801

Conductors:
Coated annealed copper.
ASTM B-33 and B-189.
Concentric stranded class B (7 strands).
ASTM B-8, UL-44 paragraph 12.4 and UL-62 paragraph 10.2 (A suitable separator is applied between the conductor and insulation to facilitate stripping).

Insulation:
VW-1 crooslinked polyethylene (thermoset)

Cabling:
Three or more conductors are assembled round with flame resistant, non-hygroscopic and non-wicking neoprene fillers as needed. A flame resistant, non-hygroscopic and non-wicking tape binder is applied over the assembly. Two conductors are assembled flat parallel (round with neoprene fillers as needed, is available upon request).

Overall Jacket:
Heavy duty, flame and sunlight resistant hypalon® (black) (thermoset)

Color Coding:
ICEA Method 1 using solid colors with stripes in accordance with Table K-2

Scope:
This specification covers multiconductors having stranded coated copper conductors flame resistant crosslinked polyethlene insulation and a heavy duty flame and sunlight resistant Hypalon jacket. Cables conform to Article 318 cable trays and Article 340 power and control cable. Type TC of the 1984 NEC subject 1277 of underwriters laboratories Inc. and ICEA S-66-524, and meet the requirements of the 70,000 BTU cable tray propagation test per IEEE-383 cables are rated 600 volts 90°C dry and wet. Size 14, 12 and 10 AWG conductors are XHHW rated (VW-1). Also meets IEEE-1202, ICEA 1-29-520, T30-520 and FT-4.

Applications:
UL listed and OSHA acceptable.
Recognized for use in Class 1, Division 2 hazardous locations and for installation in trays, wireways, troughs, channels, ducts, conduit and aerially where supported by a messenger.
Specifically approved for direct burial, wet and dry locations and outdoors in cable trays where a sunlight resistant rating is required.
Designed for control, power, lighting, telemetering, signal and relay or traffic control where a low loss high temperature insulation is specified.