Belden 6051 14 and 10 AWG 600V TECK 90 Composite Armored Cable

Belden 6051 14 and 10 AWG 600V TECK 90 Composite Armored Cable

Belden 6051 14 and 10 AWG 600V TECK 90 Composite Armored Cable

Description:
• Composite 14 AWG stranded (7x22) and 10 AWG stranded (7x18) bare copper conductors, 12 AWG bare copper ground wire, .031x1A;(.79mm) XLPE insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.

Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 12
• Ground Wire Stranding: 7x20
• Conductor Material: BC - Bare Copper

Insulation:
• Material: XLP - Cross Linked Polyolefin

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.600
• Nom. Dia. (mm): 14.630
• Outer Jacket over Armor (y/n): Y

Outer Jacket over Armor:
• OJ Over Armor Material: PVC - Polyvinyl Chloride
• Dia. (mm): 22.7838

Armor:
• Armor Type: Interlocked
• Armor Material: Aluminum
• Diameter over Armor: 0.801

Mechanical Charactertistics (Overall):
• Installation Temperature Range: -25°C To +90°C
• Wet Temperature Range: -40°C To +90°C
• Dry Temperature Range: -40°C To +90°C
• Bulk Cable Weight: 432 lbs/1000 ft.
• Max. Recommended Pulling Tension: 200 lbs.
• Min. Bend Radius/Minor Axis: 10.800 in.

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CSA Specification: C22.2 #131; Hazardous Location; C22.2 #0.3 Clause 4.31 Low Acid Gas
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 2.5 (14 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 1.1 (10 AWG)
• Max. Recommended Current: 12 Amps/Conductor @ 25°C (14 AWG)
• Max. Recommended Current: 24 Amps/Conductor @ 25°C (10 AWG)

Flame Test:
• CSA Flame Test: FT4

Suitability:
• Sunlight Resistance: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No

technical specification:
awg 14 and 10
# conductors 6
stranding 7x22 and 7x18
no. of conductors 6
conductor material bare copper
outer shield - material unshielded
overall cable- nominal dia. (mm) -
belden cable part number 6051

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.