Eutex Cable 4 Pairs 2 Conductors 1 Nominal Area RFOU (i) S1/S5 Instrumentation 250V Flame Retardant Cable EUT-01C-04P001-Y

Eutex Cable 4 Pairs 2 Conductors 1 Nominal Area RFOU (i) S1/S5 Instrumentation 250V Flame Retardant Cable EUT-01C-04P001-Y

Select gauge from drop-down menu for prices:

Eutex Cable 4 Pairs 2 Conductors 1 Nominal Area RFOU (i) S1/S5 Instrumentation 250V Flame Retardant Cable EUT-01C-04P001-Y
Eutex Cable 4 Pairs 2 Conductors 1 Nominal Area RFOU (i) S1/S5 Instrumentation 250V Flame Retardant Cable EUT-01C-04P001-Y

Conductor: Tinned stranded compacted copper IEC 60228 class 2 

Insulation: Halogen free EPR compound 

Individual Screen: Copper/polyester tape Tinned copper train wire

Bedding: Halogen free compound

Armour: Tinned copper wire braid according to IEC 60092-376:2003

Outer Sheath: SHF2 MUD thermoset compound Halogen free & MUD resistant

Pair/Triple Identification 
• Pair: Black Light Blue 
• Triple: Light Blue Black Brown (Pairs/triples progressively numbered) 
• Sheath color: Grey (Blue for intrinsically safe) 

Sheath Marking:
• RFOU(i) S1/S5 250 V n x p(trp) x s mm² 
• NEK 606:2004 IEC 60332-3-22 QA ref Metric marking

technical specification:
construction (mm²) 4x2x1
insulation thickness (mm)
0.6
under armor diameter (mm) 15.0
outer sheath thickness (mm)
1.5
overall diameter (approx) (mm) 20.0
weight (approx) (kg/km) 510
bending radius (mm) 115
conductor resistance at 20°c (ω/km) 20.7
Eutex cable part number EUT-01C-04P001-Y
Application Standard :
design and construction iec 60092-376:2003
nominal voltage uo/u 250 v
operating temperature 90°c
flame retardancy iec 60332-1, iec 60332-3-22
corrosivity iec 60754-1, iec 60754-2
smoke density iec 61034-2
mud resistance nek 606:2004
on request cold bend and impact test (–40°c) csa c22.2 no 38-95