Prysmian and Draka Cable 2 Cores 6 Cross-section core BFCU 0.6/1kV Power, Fire Resistant and Halogen free Cable 840249

Prysmian and Draka Cable 2 Cores 6 Cross-section core BFCU 0.6/1kV Power, Fire Resistant and Halogen free Cable 840249

Select gauge from drop-down menu for prices:

Prysmian and Draka Cable 2 Cores 6 Cross-section core BFCU 0.6/1kV Power, Fire Resistant and Halogen free Cable 840249
Prysmian and Draka Cable 2 Cores 6 Cross-section core BFCU 0.6/1kV Power, Fire Resistant and Halogen free Cable 840249

Conductor: Tinned stranded circular copper, BS 6360, class 2

Insulation: Mica glass tape / EP-rubber, GP4 to BS 7655: section 1.2

Lay up / Shielding: Cores laid up in concentric layers

Inner covering: Flame retardant and halogen-free thermoplastic EP-rubber based compound

Tape over inner covering: PET tape + rubberized Polyamide tape

Armour/screen: Galvanized steel wire braid

Tape over armour/screen: PET + tape rubberised Polyamide tape

Outer sheath: Flame retardant, halogen-free, enhanced oil-resisting thermoset compound (LSF), SW4 to BS 7655 section 2.6

Marking text: "metre mark" "year" "DRAKA" "BFCU" "UKOOA code" "600/1000V" "number of cores" "conductor size" "BS7917" "IEC60331-21" "IEC60332-3-22" (marking may differ on cable actually supplied)

Outer sheath colour: Black

Operating temperature: 90°C

Operating Voltage: 0.6/1kV

Standards applied:
• BS7917/BS6883/UKOOA - Design
• BS6360 class 2 - Conductor
• BS7655 section 1.2 - Insulation
• BS7655 section 2.6 - Sheath
• IEC 60332-1 & 3-22 - Flame Retardant
• IEC60331-21 - Fire Resistant
• IEC60754-1,2 - Halogen Free
• IEC 61034-1,2 - Low Smoke

Core identification: All cores are offwhite with black numbers No 1,2,3....

Description:
• BFCU 0.6/1kV 2X 1.5mm2
• BFCU 0.6/1kV 2X 2.5mm2
• BFCU 0.6/1kV 2X 4mm2
• BFCU 0.6/1kV 2X 6mm2
• BFCU 0.6/1kV 2X 10mm2
• BFCU 0.6/1kV 2X 16mm2
• BFCU 0.6/1kV 2X 35mm2
• BFCU 0.6/1kV 3X 1.5mm2
• BFCU 0.6/1kV 3X 2.5mm2
• BFCU 0.6/1kV 3X 4mm2
• BFCU 0.6/1kV 3X 6mm2
• BFCU 0.6/1kV 3X 10mm2
• BFCU 0.6/1kV 3X 16mm2
• BFCU 0.6/1kV 3X 25mm2
• BFCU 0.6/1kV 3X 35mm2
• BFCU 0.6/1kV 3X 50mm2
• BFCU 0.6/1kV 3X 70mm2
• BFCU 0.6/1kV 3X 95mm2
• BFCU 0.6/1kV 4X 1.5mm2
• BFCU 0.6/1kV 4X 2.5mm2
• BFCU 0.6/1kV 4X 4mm2
• BFCU 0.6/1kV 4X 6mm2
• BFCU 0.6/1kV 4X 35mm2
• BFCU 0.6/1kV 4X 70mm2
• BFCU 0.6/1kV 7X 1.5mm2
• BFCU 0.6/1kV 7X 2.5mm2
• BFCU 0.6/1kV 12X 1.5mm2
• BFCU 0.6/1kV 12X 2.5mm2
• BFCU 0.6/1kV 19X 2.5mm2
• BFCU 0.6/1kV 27X 2.5mm2

Sheath Colour: BLACK

Design standard:
• BS 7917 : 1999
• BS 6883 : 1991

Application:
• Armoured cable for fixed installation for power, control or lighting in both EX and safe areas, emergency and critical systems where there is a requirement for fire reistant cables.
• Enhanced MUD resistant version also available for use in areas exposed to mud and drilling / cleaning fluids, meeting the mud resistance requirement in NEK 606.

technical specification:
number of cores 2
cross-section core, mm2 6
conductor diameter, mm 3.15
insulation thickness, mm 1
thickness inner sheath, mm 1.2
approx. diameter inner sheath, mm 13.5
diameter braid wire, mm 0.3
thickness outer sheath, mm 1.4
approx. overall diameter, mm 18
weight of cable approx. (kg/km) 570
copper content approx. (kg/km) 109
max. conductor resistance at 20°c, ohm/km 3.11
max. conductor resistance at 90°c, ohm/km 3.97
reactance at 50hz, ohm/km 0.094
reactance at 60hz, ohm/km 0.112
current rating iec 60092-352 table b.4, ampere 44
short circuit rating 1 second, ampere 840
ukooa code yd206
prysmian and draka cable part number 840249

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question