General Cable ACWU90® 4C 1 AWG XLPE AIA PVC Low Voltage Power Armored 600V CSA

General Cable ACWU90® 4C 1 AWG XLPE AIA PVC Low Voltage Power Armored 600V CSA

ACWU90 4C 1 AWG XLPE AIA PVC Low Voltage Power Armored 600V CSA

Conductor: 2 AWG thru 750 kcmil bare ACM aluminum (8000 series aluminum) compact Class B strand

Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: 2 AWG—black, white and red; 1 AWG to 750 kcmil—per ICEA Method 4, individual conductors colored black with conductor number surface printed in contrasting ink

Ground (Bonding) Conductor: The conductor consists of one uninsulate stranded bare aluminum (ACM) conductor

Armor: Aluminum Interlocked Armor (AIA)

Jacket: ACID-FLAME-CHECK ??® flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black

Applications:
• For exposed and concealed wiring in dry, damp or wet locations
• For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required by inspection authority)
• For wiring in all hazardous locations when used with certified HL cable glands
• For service entrance installations

Features:
• Rated at 90°C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Cost-effective alternative to installations in conduit
• Meets cold bend and impact tests at -40°C

Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 51 and No. 174
• CSA Approval File Number 157657

Flame Test Compliances: CSA FT1 and FT4

Other Compliances:
• Hazardous Location Rating: HL
• OSHA Acceptable

Packaging: For Canadian customers, nominal standard lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for cut to length, lagging and pulling eyes

technical specifications:
cond. size (awg/kcmil) 1
cond. strand 8/.108
nominal conductor o.d.(inches) 0.298
nominal conductor o.d.(mm) 7.569
min. avg. insulation thickness(inches) 0.050
min. avg. insulation thickness(mm) 1.270
nominal diameter (over)(insulation in inches) 0.400
nominal diameter (over)(insulation in mm) 10.160
nominal diameter (over)(armor in inches) 1.210
nominal diameter (over)(armor in mm) 30.734
nominal diameter (over)(cable in inches) 1.323
nominal diameter (over)(cable in mm) 33.604
aluminum weight*(lbs/1000 ft) 279
aluminum weight*(kg/km) 402
net weight( lbs/1000 ft)
627
net weight(kg/km) 912
90?c ampacity** (30°c ambient) 115
catalog number 11281.040100