Belden 28430 14 and 8 AWG 6 Conductors 600V Type MC Metal Clad Steel Cable
Select gauge from drop-down menu for prices:
Description:
• Composite 14 AWG (7x22) and 8 AWG (7x16) stranded bare copper conductors, 10 AWG bare copper ground wire, steel interlocked armor, cross-linked
polyethylene insulation, PVC jacket.
Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 10
• Ground Wire Stranding: 7x18
• Ground Wire Conductor Material: BC - Bare Copper
Insulation:
• Material: XLPE - Cross Linked Polyethylene
• Wall Thickness (mm): 0.762 (14 AWG)
• Wall Thickness (mm): 1.143 (8 AWG)
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.27
• Outer Jacket over Armor (y/n): Y
Armor:
• Armor Type: Interlocked
• Armor Material: Steel
• Diameter over Armor: 0.83
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -40°C To +90°C
• Wet Temperature Range: -40°C To +90°C
• Dry Temperature Range: -40°C To +90°C
• Bulk Cable Weight: 745.588 Kg/Km
• Max. Recommended Pulling Tension: 1934.970 N
• Min. Bend Radius/Minor Axis: 284.480 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: MC, XHHW-2 Singles, UL1569
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/13/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 2.09984 (8 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 8.5306 (14 AWG)
• Max. Operating Voltage - UL: 600 V RMS
• Max. Recommended Current: 12 Amps/conductor @ 25°C (14 AWG)
• Max. Recommended Current: 44 Amps/conductor @ 25°C (8 AWG)
Flame Test:
• UL Flame Test: UL1685 UL Loading
Suitability:
• Suitability - Burial: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 14 and 8 |
# conductors | 6 |
stranding | 7x22 and 7x16 |
no. of conductors | 6 |
conductor material | bare copper |
outer shield - material | unshielded |
overall cable- nominal dia. (mm) | 23.876 |
belden cable part number - steel | 28430 |