Belden 3028A 18 AWG 2 Triads 300V PLTC Cable
Select gauge from drop-down menu for prices:
- Belden 18 AWG 300V PLTC Individually and Overall Beldfoil Shield Triads Orange Communication Cable
- Belden 3031A 18 AWG 4 Triads 300V PLTC Cable
- Belden 3033A 18 AWG 8 Triads 300V PLTC Cable
- Belden 3068A 18 AWG 12 Triads 300V PLTC Cable
- Belden 3037A 18 AWG 16 Triads 300V PLTC Cable
- Belden 3039A 18 AWG 24 Triads 300V PLTC Cable
Description:
• 18 AWG triads stranded (7x26) bare copper conductors, twisted triads, PVC insulation, individually shielded plus an overall Beldfoil (100% coverage), PVC jacket.
Insulation:
• Material: PVC - Polyvinyl Chloride
Communication Wire:
• AWG: 22
• Material: BC - Bare Copper
• Stranding: 7x30
Inner Shield:
• Trade Name: Beldfoil®
• Type: Tape
• Material: Aluminum Foil-Polyester Tape
Inner Shield Drian Wire AWG:
• AWG: 20
• Stranding: 7x28
• Material: TC - Tinned Copper
Outer Shield Drian Wire AWG:
• AWG: 18
• Stranding: 7x26
• Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.397
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• Operating Temperature Range: -30°C To +105°C
• Bulk Cable Weight: 110 lbs/1000 ft.
• Max. Recommended Pulling Tension: 175 lbs.
• Min. Bend Radius/Minor Axis: 4.500 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: PLTC, ITC, CMG
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Inductance (?H/ft): 0.17
• Nom. Capacitance Conductor to Conductor (pF/ft): 54
• Nom. Capacitance Cond. to Other Conductor and Shield (pF/ft): 101
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 5.86 (18 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 14.7 (22 AWG)
• Nom. Inner Shield DC Resistance @ 20°C (Ohm/1000 ft): 10.3
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 3.9
• Max. Operating Voltage - UL: 300 V RMS
Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• CSA Flame Test: FT4
• IEEE Flame Test: 1202
• ICEA Flame Test: T-29-520
Suitability:
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 18 |
# triads | 2 |
stranding | 7x26 |
no. of conductors | 7 |
conductor material | bare copper |
outer shield - type | tape |
outer shield - material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 11.430 |
belden cable part number | 3028A |