Belden 82743 Cable 22 AWG 6 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor Flamarrest Jacket Cable
Select gauge from drop-down menu for prices:
- Belden Cable Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor Paired Cable
- Belden 88741 Cable 22 AWG 2 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor FEP Jacket Cable
- Belden 88757 Cable 22 AWG 4 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor FEP Jacket Cable
- Belden 82741 Cable 22 AWG 2 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor Flamarrest Jacket Cable
- Belden 82742 Cable 22 AWG 3 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor Flamarrest Jacket Cable
- Belden 82757 Cable 22 AWG 4 Pairs Unshielded Plenum Rated Audio Control and Instrumentation Multi Conductor Flamarrest Jacket Cable
Description:
• 22 AWG stranded (7x30) tinned copper conductors, plenum, FEP insulation, twisted pairs, Flamarrest® jacket.
Insulation:
• Material: FEP - Fluorinated Ethylene Propylene
• Wall Thickness (mm): 0.178
Outer Jacket:
• Trade Name: Flamarrest®
• Material: LS PVC - Low Smoke Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.381
Mechanical Charactertistics (Overall):
• Operating Temperature Range: 0°C To +75°C
• Bulk Cable Weight: 62.504 Kg/Km
• Max. Recommended Pulling Tension: 484.854 N
• Min. Bend Radius/Minor Axis: 63.500 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMP
• CEC/C(UL) Specification: CMP
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 10/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Characteristic Impedance (Ohm): 80
• Nom. Inductance (μH/m): 0.49215
• Nom. Capacitance Conductor to Conductor (pF/m): 68.901
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 52.496
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 3.3 Amps/Conductor @ 25°C (10°C rise in temp)
Flame Test:
• UL Flame Test: NFPA 262
• C(UL) Flame Test: FT6
Plenum/Non-Plenum:
• Plenum (Y/N): Yes
technical specification: | |
awg | 22 |
# pairs | 6 |
stranding | 7x30 |
no. of conductors | 12 |
conductor material | tinned copper |
outer shield - material | unshielded |
overall cable- nominal dia. (mm) | 6.045 |
belden cable part number | 82743 |