Belden 8723 22 AWG 2 Pairs Shielded Twisted Paired PVC Jacket Cable

Belden 8723 22 AWG 2 Pairs Shielded Twisted Paired PVC Jacket Cable

Select gauge from drop-down menu for prices:

Belden 8723 22 AWG 2 Pairs Shielded Twisted Paired PVC Jacket Cable

Precio habitual $0.00 $1.42 Oferta /per Foot

Belden 8723 22 AWG 2 Pairs Shielded Twisted Paired PVC Jacket Cable

Description:
• 22 AWG stranded (7x30) tinned copper conductors, polypropylene insulation, twisted pairs, individually Beldfoil® shielded (100% coverage), 24 AWG stranded tinned copper drain wire, PVC jacket.

Insulation:
• Material: PP - Polypropylene
• Wall Thickness (mm): 0.229

Inner Shield Drain Wire AWG:
• AWG: 24
• Stranding: 7x32
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.508

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -20°C To +75°C
• UL Temperature Rating: 60°C
• Bulk Cable Weight: 25.299 Kg/Km
• Max. Recommended Pulling Tension: 186.824 N
• Min. Bend Radius/Minor Axis: 44.450 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CM
• CEC/C(UL) Specification: CM
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Characteristic Impedance (Ohm): 52.000
• Nom. Inductance (μH/m): 0.55777
• Nom. Capacitance Conductor to Conductor (pF/m): 108.273
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/m): 203.422
• Nominal Velocity of Propagation (VP %): 66
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 48.2307
• Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: 49.215 Ohm/km
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 2.3 Amps/Conductor @ 25°C

Flame Test:
• UL Flame Test: UL1685 UL Loading

Plenum/Non-Plenum:
• Plenum (Y/N): No
• Plenum Number: 82723, 87723, 88723

technical specification:
awg 22
# pairs 2
stranding 7x30
no. of conductors 4
conductor material tinned copper
outer shield - material unshielded
overall cable- nominal dia. (mm) 4.064
belden cable part number 8723